L8-09: Output Ground Fault Detection
No.
Name
(Hex.)
L8-09
Output Ground Fault
Detection
(04B5)
0 : Disabled
The drive will not detect ground faults.
1 : Enabled
If there is high leakage current or a ground short circuit in one or two output phases, the drive will detect GF
[Ground Fault].
Note:
If the ground path impedance is low, oC [Overcurrent], SC [Out Short Circuit or IGBT Fault], or ov [DC Bus Overvoltage] can stop the
motor.
L8-10: Heatsink Fan Operation Selection
No.
Name
(Hex.)
L8-10
Heatsink Fan Operation
Selection
(04B6)
0 : During Run, w/ L8-11 Off-Delay
The drive turns on the fan when a Run command is active.
1 : Always On
The fan turns on when you supply power to the drive. When you release the Run command and the delay time set
in L8-11 [HeatsinkCoolingFan Off DelayTime] is expired, the fan stops. his setting extends the fan lifetime.
2 : On when Drive Temp Reaches L8-64
The fan turns on when the drive detects that the main circuit is overheating.
L8-11: Heatsink Fan Off-Delay Time
No.
Name
(Hex.)
L8-11
Heatsink Fan Off-Delay
Time
(04B7)
L8-12: Ambient Temperature Setting
No.
Name
(Hex.)
L8-12
Ambient Temperature
Setting
(04B8)
Note:
The setting range changes when the L8-35 [Installation Method Selection] value changes:
• 0 [IP20/UL Open Type]: -10 °C to +60 °C
• 1 [Side-by-Side Mounting]: -10 °C to +50 °C
• 2 [IP20/UL Type 1]: -10 °C to +50 °C
• 3 [External Heatsink]: -10 °C to +50 °C
The drive automatically adjusts the drive rated current to the best value as specified by the set temperature. Set the
ambient temperature of the area where you install the drive to a value that is more than the drive rating.
Refer to
Derating Depending on Ambient Temperature on page 324
ambient temperature.
YASKAWA SIEPC71061753A GA500 Technical Manual
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the function to enable and disable ground fault protection.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets operation of the heatsink cooling fan.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the length of time that the drive will wait before it stops the cooling fan after it cancels the
Run command when L8-10 = 0 [Heatsink Cooling Fan Ope Select = Dur Run (OffDly)].
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the ambient temperature of the drive installation area.
12.9 L: Protection Functions
Description
Description
Description
Description
for information about derating as specified by
Default
(Range)
Determined by o2-04
(0, 1)
Default
(Range)
0
(0 - 2)
Default
(Range)
60 s
(0 - 300 s)
Default
(Range)
40 °C
(-10 °C - +60 °C)
12