12.8 H: Terminal Function Selection
■
H2-62: Term MA,MB,MC Minimum ON Time
No.
Name
(Hex.)
H2-62
Term MA,MB,MC
Minimum ON Time
(1B48)
Expert
■
H2-63: Terminal P1 Secondary Function
No.
Name
(Hex.)
H2-63
Terminal P1 Secondary
Function
(1B49)
Expert
■
H2-64: Terminal P1 Logical Operation
No.
Name
(Hex.)
H2-64
Terminal P1 Logical
Operation
(1B4A)
Expert
Note:
Refer to
Output of Logical Operation Results of MFDO on page 621
and logical operations.
■
H2-65: Terminal P1 Minimum ON Time
No.
Name
(Hex.)
H2-65
Terminal P1 Minimum ON
Time
(1B4B)
Expert
■
H2-66: Terminal P2 Secondary Function
No.
Name
(Hex.)
H2-66
Terminal P2 Secondary
Function
(1B4C)
Expert
■
H2-67: Terminal P2 Logical Operation
No.
Name
(Hex.)
H2-67
Terminal P2 Logical
Operation
(1B4D)
Expert
Note:
Refer to
Output of Logical Operation Results of MFDO on page 621
and logical operations.
■
H2-68: Terminal P2 Minimum ON Time
No.
Name
(Hex.)
H2-68
Terminal P2 Minimum ON
Time
(1B4E)
Expert
◆
MFDO Setting Value
Selects the function configured to a MFDO.
628
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the minimum ON time that the drive uses to output the logical calculation results from
terminal MA/MB-MC.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the second function for terminal P1-C1. Outputs the logical calculation results of the
terminals assigned to functions by H2-02 [Term P1 Function Selection].
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the logical operation for the functions set in H2-02 [Term P1 Function Selection] and H2-63
[Terminal P1 Secondary Function].
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the minimum ON time used to output the logical calculation results from terminal P1-C1.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the second function for terminal P2-C2. Outputs the logical calculation results of the
terminals assigned to functions by H2-03 [Term P2 Function Selection].
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the logical operation for the functions set in H2-03 [Term P2 Function Selection] and H2-66
[Terminal P2 Secondary Function].
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the minimum ON time used to output the logical calculation results from terminal P2-C2.
Description
Description
Description
for more information about the relation between parameter settings
Description
Description
Description
for more information about the relation between parameter settings
Description
YASKAWA SIEPC71061753A GA500 Technical Manual
Default
(Range)
0.1 s
(0.0 - 25.0 s)
Default
(Range)
F
(0 - FF)
Default
(Range)
0
(0 - 8)
Default
(Range)
0.1 s
(0.0 - 25.0 s)
Default
(Range)
F
(0 - FF)
Default
(Range)
0
(0 - 8)
Default
(Range)
0.1 s
(0.0 - 25.0 s)