7.6 Parameter Setting Errors
Code
Name
oPE10
V/f Data Setting Error
Code
Name
oPE11
Carrier Frequency Setting Error
Code
Name
oPE13
Pulse Monitor Selection Error
Code
Name
oPE16
Energy Saving Constants Error
Code
Name
oPE33
Digital Output Selection Error
272
Causes
The parameters that set the V/f pattern do not
satisfy these conditions:
• For motor 1: E1-09 ≤ E1-07 < E1-06 ≤ E1-11 ≤
E1-04 [Minimum Output Frequency ≤ Mid Point
A Frequency < Base Frequency ≤ Mid Point B
Frequency ≤ Maximum Output Frequency]
• For motor 2: E3-09 ≤ E3-07 < E3-06 ≤ E3-11 ≤
E3-04 [Minimum Output Frequency ≤ Mid Point
A Frequency < Base Frequency ≤ Mid Point B
Frequency ≤ Maximum Output Frequency]
Causes
These parameters are set at the same time:
• C6-05 > 6 [Carrier Freq Proportional Gain >
6]
• C6-04 > C6-03 [Carrier Frequency Lower Limit
> Carrier Frequency Upper Limit]
Note:
When C6-05 < 7, C6-04 becomes disabled. The
drive sets the carrier frequency to the value set
to C6-03.
C6-02 to C6-05 settings are not in the applicable
setting range.
Causes
H6-06 = 101, 102, 105, or 116 [Terminal MP
Monitor Selection = Frequency Reference, Output
Frequency, Motor Speed, Output Frequency after
Soft Starter] has not been set when H6-07 = 0
[Terminal MP Frequency Scaling = 0 Hz].
Causes
The Energy Saving parameters are not set in the
applicable setting range.
Causes
These two parameters are set at the same time:
• H2-60 ≠ F [Term MA,MB,MC Secondary
Function ≠ Not Used]
• H2-01 = 1xx [Term MA,MB,MC Function
Selection = Inverse output of xx]
These two parameters are set at the same time:
• H2-63 ≠ F [Terminal P1 Secondary Function ≠
Not Used]
• H2-02 = 1xx [Term P1 Function Selection =
Inverse output of xx]
These two parameters are set at the same time:
• H2-66 ≠ F [Terminal P2 Secondary Function ≠
Not Used]
• H2-03 = 1xx [Term P2 Function Selection =
Inverse output of xx]
These parameter pairs are set incorrectly:
• H2-21 [Comparator 1 Lower Limit] > H2-22
[Comparator 1 Upper Limit]
• H2-27 [Comparator 2 Lower Limit] > H2-28
[Comparator 2 Upper Limit]
Possible Solutions
Set the parameters correctly to satisfy the conditions.
Possible Solutions
Set C6-02 to C6-05 correctly.
Possible Solutions
Set H6-06 correctly.
Possible Solutions
Make sure that E5-xx is set correctly as specified by the motor
nameplate data.
Possible Solutions
Clear the H2-01 to H2-03 = 1xx [Inverse output of xx] settings.
Note:
If you use the function to output logical calculation results
(H2-60, H2-63, H2-66 ≠ F), you cannot set H2-01 to H2-03 =
1xx.
• Set parameters H2-21 ≤ H2-22.
• Set parameters H2-27 ≤ H2-28.