Note:
Refer to this table for Drive Mode and Programming Mode functions.
Mode
Drive Mode
Monitors
Parameters
User Custom Parameters
Parameter Backup/Restore
Programming Mode
Modified Parameters/Fault Log
Auto-Tuning
Initial Setup
Diagnostic Tools
0 : Disregard RUN while Programming
The drive rejects the Run command while in Programming Mode.
1 : Accept RUN while Programming
The drive accepts a Run command entered from an external source while in Programming Mode.
2 : Allow Programming Only at Stop
The drive does not let the user enter Programming Mode when the drive is operating. The drive does not show the
Programming Mode when a Run command is active.
b1-14: Phase Order Selection
No.
Name
(Hex.)
b1-14
Phase Order Selection
(01C3)
0 : Standard
1 : Switch Phase Order
b1-15: Frequency Reference Selection 2
No.
Name
(Hex.)
b1-15
Frequency Reference
Selection 2
(01C4)
This parameter is enabled when H1-xx = 2 [MFDI Function Selection = External Reference 1/2 Selection] is
activated.
Note:
• Push
on the keypad to set the input mode to LOCAL and use the keypad to enter the frequency reference.
• If the frequency reference is 0 Hz or less than or equal to the value set in E1-09 [Minimum Output Frequency] and the drive receives
the Run command, the RUN LED on the keypad will flash. Examine the setting for the frequency reference input and enter a value
more than or equal to E1-09.
0 : Keypad
Use the keypad to enter the frequency reference.
Use
and
on the keypad to change the frequency reference.
1 : Analog Input
Use MFAI terminals A1 and A2 to input an analog frequency reference with a voltage or current input signal.
• Voltage Input
Refer to
Table 12.25
to use a voltage signal input to one of the MFAI terminals.
YASKAWA SIEPC71061753A GA500 Technical Manual
Keypad Screen
Sets monitor display.
Changes parameter settings.
Shows the User Parameters.
Saves parameters to the keypad as backup.
Shows modified parameters and fault history.
Auto-Tunes the drive.
Changes initial settings.
Sets data logs and backlight.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the phase order for output terminals U/T1, V/T2, and W/T3. This parameter can align the
Forward Run command from the drive and the forward direction of the motor without changing
wiring.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the input method for frequency reference 2.
Function
Description
Description
12.3 b: Application
Default
(Range)
0
(0, 1)
Default
(Range)
0
(0 - 4)
12
483