You can continue to view parameter setting values when the terminal is OFF [Parameters Cannot be Edited].
ON : Program Lockout
OFF : Parameter Write Prohibit
1E: Reference Sample Hold
Setting Value
Function
1E
Reference Sample Hold
When the terminal is active for 100 ms, this function reads a sample of the analog frequency reference and holds
that sample. When you input the sample/hold command again, the function again reads a sample of the analog
frequency reference and holds that sample. When you turn off the power, the drive erases the saved analog
frequency and resets the frequency reference to 0.
Figure 12.70
shows an example of how the function operates.
You cannot set the Reference Sample Hold function at the same time as these functions:
• H1-xx = A [Accel/Decel Ramp Hold]
• H1-xx = 10, 11 [Up Command, Down Command]
• H1-xx = 44 to 46 [Add Offset Frequency 1 to 3]
• H1-xx = 75, 76 [Up 2 Command, Down 2 Command]
If you set them at the same time, the drive will detect oPE03 [Multi-Function Input Setting Err].
20 to 2F: External Fault
Setting Value
Function
20 to 2F
External fault
If an external fault is input to the drive, the keypad will show EFx [External Fault (Terminal Sx)], where x is the
number of the terminal (terminal Sx) to which the external fault signal is assigned. For example, when an external
fault signal is input to terminal S3, the keypad will show EF3.
Use these conditions to select the value to set in H1-xx:
• Signal input method from peripheral devices
• External fault detection method
• Motor stopping method (operation after external fault detection)
Table 12.58
shows the relation between the conditions and the value set to H1-xx.
Signal Input Method from
Peripheral Devices
Setting
N.O.
20
x
21
-
22
x
23
-
24
x
YASKAWA SIEPC71061753A GA500 Technical Manual
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the command to sample the frequency reference at terminal A1 or A2, and hold the frequency reference at that frequency.
Figure 12.70 Reference Sample Hold
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets a command to stop the drive when a failure or fault occurs on an external device.
Table 12.58 Stopping Methods for External Fault
External Fault Detection Method
*1
*2
Detected
Always
N.C.
during RUN
Detected
Only
-
x
x
x
-
-
x
-
-
x
12.8 H: Terminal Function Selection
Description
Description
Ramp to Stop
Coast to Stop
(Fault)
(Fault)
-
x
-
x
x
x
x
x
-
-
x
Stopping Method
Continuous
Fast Stop
Operation
(Fault)
(Alarm Only)
-
-
-
-
-
-
-
-
-
-
-
-
-
-
12
611