12.3 b: Application
b5-91: EZ Sleep Minimum Speed
No.
Name
(Hex.)
b5-91
EZ Sleep Minimum Speed
(0B91)
RUN
Note:
The value of b5-90 [EZ Sleep Unit] sets the units. When b5-90 changes, this parameter does not automatically update. Set this parameter
again after you change b5-90 is changed.
b5-92: EZ Sleep Level
No.
Name
(Hex.)
b5-92
EZ Sleep Level
(0B92)
RUN
Note:
When b5-90 [EZ Sleep Unit] changes, this parameter does not automatically update. Set this parameter again after you change b5-90.
b5-93: EZ Sleep Time
No.
Name
(Hex.)
b5-93
EZ Sleep Time
(0B93)
RUN
b5-94: EZ Sleep Wake-up Level
No.
Name
(Hex.)
b5-94
EZ Sleep Wake-up Level
(0B94)
RUN
Note:
The values of b5-20 [PID Unit Selection], b5-38 [PID User Unit Display Scaling], and b5-39 [PID User Unit Display Digits] set the
units. When b5-20, b5-38, and b5-39 change, this parameter does not automatically update. Set this parameter again after you change
b5-20, b5-38, and b5-39 are changed.
• When b5-95 = 0 [EZ Sleep Wake-up Mode = Absolute]:
When b5-09 = 0 [PID Output Level Selection = Normal Output (Direct Acting)], and the PID Feedback [H3-xx
= B] is less than the value of b5-94 for a time longer than the value of b5-96 [EZ Sleep Wake-up Time], the
drive will exit sleep and start operation again. When b5-09 = 1 [Reverse Output (Reverse Acting)], and the PID
feedback is more than setting value of b5-94 for a time longer than the setting value of b5-96, the drive will exit
sleep and start operation again.
• When b5-95 = 1 [Setpoint Delta]:
When b5-09 = 0, and the PID feedback is less than the value of "PID setpoint value - b5-94" for a time longer
than the value of b5-96, the drive will exit sleep and start operation again. When b5-09 = 1, and the PID
feedback is more than the value of "PID setpoint value + b5-94" for a time longer than the setting value of b5-
96, the drive will exit sleep and start operation again.
b5-95: EZ Sleep Wake-up Mode
No.
Name
(Hex.)
b5-95
EZ Sleep Wake-up Mode
(0B95)
0 : Absolute
1 : Setpoint Delta
514
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the minimum speed for the EZ Sleep/Wakeup function. This parameter uses the largest value
from b5-91, b5-34 [PID Output Lower Limit Level], and d2-02 [Frequency Reference Lower
Limit].
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the value that the output frequency or motor speed must be less than for longer than b5-93
[EZ Sleep Time] to enter Sleep Mode.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the length of time that the output frequency or motor speed must be less than b5-92 [EZ
Sleep Level] to enter Sleep Mode.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the level at which the drive resumes operation when exiting Sleep Mode.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the wake-up mode to use when exiting Sleep Mode.
Description
Description
Description
Description
Description
YASKAWA SIEPC71061753A GA500 Technical Manual
Default
(Range)
-1
0.0 Hz or 0 min
(r/min)
(0.0 to 590.0 Hz or 0 to
-1
35400 min
(r/min))
Default
(Range)
0.0 Hz or 0 min
-1
(r/min)
(0.0 to 590.0 Hz or 0 to
-1
35400 min
(r/min))
Default
(Range)
5.0 s
(0.0 - 1000.0 s)
Default
(Range)
0.00%
(0.00 - 600.00%)
Default
(Range)
0
(0, 1)