11.10 H: Terminal Functions

H3: Analog Inputs

No.
Name
(Hex.)
H3-01
Terminal A1 Signal
Level Select
(0410)
H3-02
Terminal A1 Function
Selection
(0434)
H3-03
Terminal A1 Gain
Setting
(0411)
RUN
H3-04
Terminal A1 Bias
Setting
(0412)
RUN
H3-09
Terminal A2 Signal
Level Select
(0417)
H3-10
Terminal A2 Function
Selection
(0418)
H3-11
Terminal A2 Gain
Setting
(0419)
RUN
H3-12
Terminal A2 Bias
Setting
(041A)
RUN
H3-13
Analog Input FilterTime
Constant
(041B)
H3-14
Analog Input Terminal
Enable Sel
(041C)
H3-16
Terminal A1 Offset
(02F0)
H3-17
Terminal A2 Offset
(02F1)
H3-40
Mbus Reg 15C1h Input
Function
(0B5C)
H3-41
Mbus Reg 15C2h Input
Function
(0B5F)
H3-42
Mbus Reg 15C3h Input
Function
(0B62)
H3-43
Mbus Reg Inputs
FilterTime Const
(117F)
H3-xx: MFAI Setting Values
Setting Value
Function
0
Frequency Reference
1
Frequency Gain
380
Description
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the input signal level for MFAI terminal A1.
0 : 0 to 10V (Lower Limit at 0)
1 : 0 V to 10 V (Without Lower Limit)
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the function for MFAI terminal A1.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the gain of the analog signal input to MFAI terminal A1.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the bias of the analog signal input to MFAI terminal A1.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the input signal level for MFAI terminal A2.
0 : 0-10V (LowLim=0)
1 : 0-10V (Without Lower Limit)
2 : 4 to 20 mA
3 : 0 to 20 mA
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the function for MFAI terminal A2.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the gain of the analog signal input to MFAI terminal A2.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the bias of the analog signal input to MFAI terminal A2.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the time constant for primary delay filters on MFAI terminals.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the enabled terminal or terminals when H1-xx = C [MFDI Function Select =
Analog Terminal Enable Selection] is ON.
1 : Terminal A1
2 : Terminal A2
7 : Terminals A1 and A2
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the offset level for analog signals input to terminal A1. Usually it is not necessary
to change this setting.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the offset level for analog signals input to terminal A2. Usually it is not necessary
to change this setting.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the MEMOBUS AI1 function.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the MEMOBUS AI2 function.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the MEMOBUS AI3 function.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the time constant to apply a primary delay filter to the MEMOBUS analog input
terminal.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
The input value from the MFAI terminal set with this function becomes the master frequency reference.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
The drive multiplies the analog frequency reference with the input value from the MFAI set with this function.
Description
YASKAWA SIEPC71061753A GA500 Technical Manual
Default
Ref.
(Range)
0
643
(0, 1)
0
643
(0 - 32)
100.0%
643
(-999.9 - +999.9%)
0.0%
644
(-999.9 - +999.9%)
2
644
(0 - 3)
0
644
(0 - 32)
100.0%
644
(-999.9 - +999.9%)
0.0%
645
(-999.9 - +999.9%)
0.03 s
645
(0.00 - 2.00 s)
7
645
(1, 2, 7)
0
645
(-500 - +500)
0
645
(-500 - +500)
F
646
(4 - 2F)
F
646
(4 - 2F)
F
646
(4 - 2F)
0.00 s
646
(0.00 - 2.00 s)
Ref.
646
646