7.5 Minor Faults/Alarms
Code
Name
CrST
Cannot Reset
Code
Name
MECHATROLINK
CyC
CommCycleSettingErr
Note:
If the drive detects this error, the terminal set to H2-01 to H2-03 = 10 [MFDO Function Selection = Alarm] will activate.
Code
Name
CyPo
Cycle Power to Accept Changes
Code
Name
dEv
Speed Deviation
Note:
• The drive detects this error if the difference between the detected speed and the speed reference is more than the setting of F1-10 for longer than F1-11.
• If the drive detects this error, the terminal set to H2-01 to H2-03 = 10 [MFDO Function Selection = Alarm] will activate.
• If the drive detects this error, it will operate the motor as specified by the stopping method set in F1-04 [Speed Deviation Detection Select].
Code
Name
dnE
Drive Disabled
Note:
If the drive detects this error, the terminal set to H2-01 to H2-03 = 10 [MFDO Function Selection = Alarm] will activate.
Code
Name
dWA2
DriveWorksEZ Alarm 2
Note:
If the drive detects this error, the terminal set to H2-01 to H2-03 = 10 [MFDO Function Selection = Alarm] will activate.
Code
Name
dWA3
DriveWorksEZ Alarm 3
Note:
If the drive detects this error, the terminal set to H2-01 to H2-03 = 10 [MFDO Function Selection = Alarm] will activate.
Code
Name
dWAL
DriveWorksEZ Alarm
Note:
If the drive detects this error, the terminal set to H2-01 to H2-03 = 10 [MFDO Function Selection = Alarm] will activate.
Code
Name
MECHATROLINK Watchdog
E5
Timer Err
Note:
• If the drive detects this error, the terminal set to H2-01 to H2-03 = 10 [MFDO Function Selection = Alarm] will activate.
• If the drive detects this error, it will operate the motor as specified by the stopping method set in F6-25 [MECHATROLINK Watchdog Error Sel].
Code
Name
FWD/REV Run Command Input
EF
Error
Note:
• If the drive detects EF, the motor will ramp to stop.
• If the drive detects this error, the terminal assigned to H2-01 to H2-03 = 10 [MFDO Function Select = Alarm] will be ON.
262
Causes
The drive received a fault reset command when a
Run command was active.
Causes
The communications cycle setting of the controller
is not in the permitted range of the
MECHATROLINK interface option.
Causes
Although F6-15 = 1 [Comm. Option Parameters
Reload = Reload Now], the drive does not update
the communication option parameters.
Causes
The load is too large.
The acceleration/deceleration times are too short.
The dEv detection level settings are incorrect.
The load is locked up.
The holding brake is stopping the motor.
Causes
A terminal set for H1-xx = 6A [Drive Enable]
turned OFF.
Causes
There was an error in the DriveWorksEZ program.
Causes
There was an error in the DriveWorksEZ program.
Causes
There was an error in the DriveWorksEZ program.
Causes
The drive detected a watchdog circuit exception
while it received data from the controller.
Causes
A forward command and a reverse command were
input at the same time for longer than 0.5 s.
Possible Solutions
Turn off the Run command then de-energize and re-energize the
drive.
Possible Solutions
Set the communications cycle of the controller in the permitted
range of the MECHATROLINK interface option.
Possible Solutions
Re-energize the drive to update the communication option
parameters.
Possible Solutions
Decrease the load.
Increase the values set in C1-01 to C1-08 [Acceleration/
Deceleration Times].
Adjust F1-10 [Speed Deviation Detection Level] and F1-11
[Speed Deviation Detect DelayTime].
Examine the machine.
Release the holding brake.
Possible Solutions
Examine the operation sequence.
Possible Solutions
Examine the DriveWorksEZ program and remove the cause of the
fault. This is not a drive fault.
Possible Solutions
Examine the DriveWorksEZ program and remove the cause of the
fault. This is not a drive fault.
Possible Solutions
Examine the DriveWorksEZ program and remove the cause of the
fault. This is not a drive fault.
Possible Solutions
Examine the MECHATROLINK cable connection. If this error
occurs frequently, examine the wiring and decrease the effects of
electrical interference as specified by these manuals:
• MECHATROLINK-II Installation Guide (MECHATROLINK
Members Association, manual number MMATDEP011)
• MECHATROLINK-III Installation Manual
(MECHATROLINK Members Association, publication
number MMATDEP018)
Possible Solutions
Examine the forward and reverse command sequence and correct
the problem.