Drive Watt Loss (With Built-In Emc Filter) - YASKAWA CIPR-GA50C series Technical Manual

Ac micro drives for industrial applications. 200 v class, three-phase input: 0.1 to 22 kw. 200 v class, single-phase input: 0.1 to 4.0 kw. 400 v class, three-phase input: 0.37 to 30 kw.
Table of Contents

Advertisement

2.5 Drive Models and Drive Watt Loss
Rated output current
Model
4044
4060

Drive Watt Loss (with Built-in EMC Filter)

Three-Phase 200 V Class
Rated output current
Model
2001E
2002E
2004E
2006E
2010E
2012E
2021E
2030E
2042E
2056E
2070E
2082E
Rated output current
Model
2001E
2002E
2004E
2006E
2010E
2012E
2021E
2030E
2042E
2056E
2070E
2082E
Single-Phase 200 V Class
Rated output current
Model
B001E
B002E
B004E
B006E
B010E
36
Carrier Frequency
A
kHz
44
2
60
2
Table 2.10 Drive Watt Loss (HD, Fc = 2 kHz)
Carrier Frequency
A
kHz
0.8
2
1.6
2
3.0
2
5.0
2
8.0
2
11.0
2
17.6
2
25.0
2
33.0
2
47.0
2
60.0
2
75.0
2
Table 2.11 Drive Watt Loss (HD, Fc = Default Setting)
Carrier Frequency
A
kHz
1.2
10
1.9
10
3.5
10
6
10
9.6
8
12.2
8
21
8
30
8
42
8
56
8
70
8
82
8
Table 2.12 Drive Watt Loss (HD, Fc = 2 kHz)
Carrier Frequency
A
kHz
0.8
2
1.6
2
3
2
5
2
8
2
Interior Unit Loss
Cooling Fin Loss
W
137
176
Interior Unit Loss
Cooling Fin Loss
W
7
8
12
20
18
24
37
46
56
78
109
133
Interior Unit Loss
Cooling Fin Loss
W
7
8
13
21
19
25
41
50
61
86
120
149
Interior Unit Loss
Cooling Fin Loss
W
8
12
17
20
34
YASKAWA SIEPC71061753A GA500 Technical Manual
Total Loss
W
W
417
554
490
666
Total Loss
W
W
4
11
7
15
13
25
22
42
37
55
49
73
83
120
163
209
200
256
269
347
411
520
439
572
Total Loss
W
W
5
12
8
16
16
29
27
48
43
62
56
81
108
149
187
237
232
293
318
404
473
593
525
674
Total Loss
W
W
4
12
7
19
13
30
23
43
37
71

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ga500 series

Table of Contents