3.3 Main Circuit Wiring
Model
Terminal
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
4038
-, +1, +2
B1, B2
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
4044
-, +1, +2
B1, B2
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
4060
-, +1, +2
B1, B2
*1
Remove insulation from the ends of wires to expose the length of wire shown.
*2
If you turn on the internal EMC filter, the leakage current of the drive will be more than 3.5 mA. Use these closed-loop crimp
terminals or equivalent to connect a protective ground wire that has a minimum cross-sectional area of 10 mm
• 8-4NS from JST Mfg. Co., Ltd.
• R8-4S from NICHIFU Co.,Ltd.
Main Circuit Wire Gauges and Tightening Torques
WARNING! Electrical Shock Hazard. Make sure that the protective ground wire conforms to technical standards and local
safety regulations. The IEC/EN 61800-5-1:2007 standard specifies that you must wire the power supply to automatically de-
energize when the protective ground wire disconnects. If you turn on the internal EMC filter, the leakage current of the drive will
be more than 3.5 mA. You can also connect a protective ground wire that has a minimum cross-sectional area of 10 mm
(copper wire). If you do not obey the standards and regulations, it can cause serious injury or death.
Note:
• The recommended wire gauges are based on drive continuous current ratings with 75 °C (167 °F) 600 V class 2 heat-resistant indoor
PVC wire. Assume these conditions:
–Ambient temperature: 40 °C (104 °F) maximum
–Wiring distance: 100 m (3281 ft) maximum
–Normal duty rated current value
• Use terminals +1, +2, -, B1, and B2 to connect peripheral options, for example a DC reactor or a braking resistor. Do not connect other
items to these terminals.
• Refer to the instruction manual for each device for recommended wire gauges to connect peripheral devices or options to terminals +1,
+2, -, B1, and B2. Contact Yaskawa or your nearest sales representative if the recommended wire gauges for the peripheral devices or
options are out of the range of the applicable gauges for the drive.
68
Recommended
Applicable Gauge
Gauge
mm
2
mm
2
10
4 - 16
6
2.5 - 10
16
4 - 25
4
2.5 - 6
10
6 - 16
16
4 - 25
10
4 - 16
16
6 - 25
6
4 - 10
10
6 - 16
25
6 - 35
16
4 - 25
25
6 - 35
10
2.5 - 16
10
6 - 16
Wire
Terminal Screw
Stripping
*1
Length
Size
mm
10
M4
10
M4
18
M5
10
M4
-
M6
18
M5
18
M5
18
M5
10
M4
-
M6
18
M5
18
M5
18
M5
10
M4
-
M6
YASKAWA SIEPC71061753A GA500 Technical Manual
Tightening Torque
N∙m (in∙lb)
Shape
1.5 - 1.7
(13.5 - 15)
1.5 - 1.7
(13.5 - 15)
2.3 - 2.5
(19.8 - 22)
1.5 - 1.7
(13.5 - 15)
5.4 - 6.0
(47.8 - 53.1)
2.3 - 2.5
(19.8 - 22)
2.3 - 2.5
(19.8 - 22)
2.3 - 2.5
(19.8 - 22)
1.5 - 1.7
(13.5 - 15)
5.4 - 6.0
(47.8 - 53.1)
• ≤ 25 mm
2
2.3 - 2.5
(19.8 - 22)
• 35 mm
2
4.1 - 4.5
(36 - 40)
2.3 - 2.5
(19.8 - 22)
• ≤ 25 mm
2
2.3 - 2.5
(19.8 - 22)
• 35 mm
2
4.1 - 4.5
(36 - 40)
1.5 - 1.7
(13.5 - 15)
5.4 - 6.0
(47.8 - 53.1)
2
(copper wire).
2