YASKAWA CIPR-GA50C series Technical Manual page 378

Ac micro drives for industrial applications. 200 v class, three-phase input: 0.1 to 22 kw. 200 v class, single-phase input: 0.1 to 4.0 kw. 400 v class, three-phase input: 0.37 to 30 kw.
Table of Contents

Advertisement

11.10 H: Terminal Functions
Setting Value
Function
16
Frequency Detection 4
17
Torque Detection 1
(N.C.)
18
Torque Detection 2
(N.O.)
19
Torque Detection 2
(N.C.)
1A
During reverse
1B
During Baseblock (N.C.)
1C
Motor 2 Selected
1E
Executing Auto-Restart
1F
Motor Overload Alarm
(oL1)
20
Drive Overheat Pre-
Alarm (oH)
21
Safe Torque OFF
22
Mechanical Weakening
Detection
2F
Maintenance
Notification
30
During Torque Limit
37
During Frequency
Output
38
Drive Enabled
39
Watt Hour Pulse Output
378
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
The terminal activates when the output frequency is higher than the value of L4-03 [Speed Agree Detection
Level(+/-)]. After the terminal activates, the terminal stays activated until the output frequency is at the value of
L4-03 - L4-04.
Note:
The detection level set with L4-03 is a signed value. The drive will only detect in one direction.
ON : The output frequency is higher than the value of L4-03.
OFF : The output frequency is less than the value of "L4-03 - L4-04," or it does not exceed the value of L4-03.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
The terminal deactivates when the drive detects overtorque or undertorque.
OFF : The output current/torque is more than the torque value set with L6-02 [Torque Detection Level 1], or the
level is less than the torque value set with L6-02 [Torque Detection Level 1] for longer than the time set with L6-03
[Torque Detection Time 1].
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
The terminal activates when the drive detects overtorque or undertorque.
ON : The output current/torque is more than the torque value set with L6-05 [Torque Detection Level 2], or the
level is less than the torque value set with L6-05 [Torque Detection Level 2] for longer than the time set with L6-06
[Torque Detection Time 2].
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
The terminal deactivates when the drive detects overtorque or undertorque.
OFF : The output current/torque is more than the torque value set with L6-05 [Torque Detection Level 2], or the
level is less than the torque value set with L6-05 [Torque Detection Level 2] for longer than the time set with L6-06
[Torque Detection Time 2].
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
The terminal activates when the motor operates in the reverse direction.
ON : The motor is operating in the reverse direction.
OFF : The motor is operating in the forward direction or the motor stopped.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
The terminal deactivates during baseblock. When the drive is in baseblock, the drive output transistor stops
switching and does not make DC bus voltage.
ON : The drive is not in baseblock.
OFF : During baseblock
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
The terminal activates when motor 2 is selected.
ON : Motor 2 Selection
OFF : Motor 1 Selection
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
The terminal activates when the Auto Restart function is trying to restart after a fault.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
The terminal activates when the electronic thermal protection value of the motor overload protective function is a
minimum of 90% of the detection level.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
The terminal activates when the drive heatsink temperature is at the level set with L8-02 [Overheat Alarm Level].
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
The terminal activates (safety stop state) when the safety circuit and safety diagnosis circuit are operating correctly
and when terminals H1-HC and H2-HC are OFF (Open).
ON : Safety stop state
OFF : Safety circuit fault or RUN/READY
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
The terminal activates when the drive detects mechanical weakening.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
The terminal activates when drive components are at their estimated maintenance period.
Tells the user about the maintenance period for these items:
• IGBT
• Cooling fan
• Capacitor
• Soft charge bypass relay
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
The terminal activates when the torque reference is the torque limit set with L7 parameters or H3-02 or H3-10
[MFAI Function Selection].
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
The terminal activates when the drive outputs frequency.
ON : The drive outputs frequency.
OFF : The drive does not output frequency.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
This terminal activates when the H1-xx = 6A [Drive Enable] terminal activates.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Outputs the pulse that shows the watt hours.
Description
YASKAWA SIEPC71061753A GA500 Technical Manual
Ref.
634
635
635
635
636
636
636
636
636
637
637
637
637
637
637
638
638