YASKAWA CIPR-GA50C series Technical Manual page 493

Ac micro drives for industrial applications. 200 v class, three-phase input: 0.1 to 22 kw. 200 v class, single-phase input: 0.1 to 4.0 kw. 400 v class, three-phase input: 0.37 to 30 kw.
Table of Contents

Advertisement

b3-04: V/f Gain during Speed Search
No.
Name
(Hex.)
b3-04
V/f Gain during Speed
Search
(0194)
Use the this formula to calculate the output voltage during Speed Search:
Output voltage during Speed Search = Configured V/f × b3-04
When the current detection search operates correctly, this configuration is not necessary.
b3-05: Speed Search Delay Time
No.
Name
(Hex.)
b3-05
Speed Search Delay Time
(0195)
When you use a magnetic contactor between the drive and motor, you must close the contactor before the drive
will do Speed Search. This parameter sets a delay time to activate the magnetic contactor.
b3-06: Speed Estimation Current Level 1
No.
Name
(Hex.)
b3-06
Speed Estimation Current
Level 1
(0196)
Expert
When the speed estimation value is the minimum output frequency, increase this setting. You can do this when the
motor coasts at a high speed while the drive estimates the speed during Speed Estimation Speed Search. The limit
of the output current during speed search is automatically the drive rated current.
Note:
When the drive cannot accurately estimate the speed after you adjust this parameter, use Current Detection Speed Search.
b3-07: Speed Estimation Current Level 2
No.
Name
(Hex.)
b3-07
Speed Estimation Current
Level 2
(0197)
Expert
During Speed Estimation Speed Searches, when the speed estimation value aligns with the minimum output
frequency, increase the setting value in 0.1-unit increments. The limit of the output current during speed search is
automatically the drive rated current.
b3-08: Speed Estimation ACR P Gain
No.
Name
(Hex.)
b3-08
Speed Estimation ACR P
Gain
(0198)
Expert
b3-09: Speed Estimation ACR I Time
No.
Name
(Hex.)
b3-09
Speed Estimation ACR I
Time
(0199)
Expert
YASKAWA SIEPC71061753A GA500 Technical Manual
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the ratio used to reduce the V/f during searches to reduce the output current during speed
searches.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the Speed Search delay time to activate a magnetic contactor installed between the drive and
motor.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the level of current that flows to the motor during Speed Estimation Speed Search as a
coefficient of the motor rated current. Usually it is not necessary to change this setting.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the level of current that flows to the motor during Speed Estimation Speed Search as a
coefficient of E2-03 [Motor No-Load Current] or E4-03 [Motor 2 Rated No-Load Current].
Usually it is not necessary to change this setting.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the proportional gain for the automatic current regulator during Speed Estimation Speed
Search. Also adjusts speed search responsiveness. Usually it is not necessary to change this
setting.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the integral time for the automatic current regulator during Speed Estimation Speed Search.
Also adjusts speed search responsiveness. Usually it is not necessary to change this setting.
Description
Description
Description
Description
Description
Description
12.3 b: Application
Default
(Range)
Determined by o2-04
(10 - 100)
Default
(Range)
0.2 s
(0.0 - 100.0 s)
Default
(Range)
Determined by o2-04
(0.0 - 2.0)
Default
(Range)
1.0
(0.0 - 3.0)
Default
(Range)
Determined by A1-02 and
o2-04
(0.00 - 6.00)
Default
(Range)
Determined by A1-02
(0.0 - 1000.0 ms)
12
493

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ga500 series

Table of Contents