11.17 U: Monitors
No.
Name
(Hex.)
U2-11
Input Terminal Status @
Fault
(008A)
U2-12
Output Terminal Status @
Fault
(008B)
U2-13
Operation Status @ Fault
(008C)
U2-14
Elapsed Time @ Fault
(008D)
U2-15
SFS Output @ Fault
(07E0)
U2-16
q-Axis Current@Fault
(07E1)
U2-17
d-Axis Current@Fault
(07E2)
U2-19
ControlDeviation@Flt
(07E4)
416
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Shows the status of the MFDI terminals at the most recent fault where
For example, U2-11 shows
Use U1-10 [Input Terminal Status] to monitor the actual MFDI terminal status.
bit0 : Terminal S1
bit1 : Terminal S2
bit2 : Terminal S3
bit3 : Terminal S4
bit4 : Terminal S5
bit5 : Terminal S6
bit6 : Terminal S7
bit7 : Not used (normal value of [ ]).
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Shows the status of the MFDO terminals at the most recent fault where
For example, U2-12 shows
Use U1-11 [Output Terminal Status] to monitor the actual MFDO terminal status.
bit0 : Terminal MA/MB-MC
bit1 : Terminal P1-C1
bit2 : Terminal P2-C2
bit3 : Not used (normal value of [ ]).
bit4 : Not used (normal value of [ ]).
bit5 : Not used (normal value of [ ]).
bit6 : Not used (normal value of [ ]).
bit7 : Not used (normal value of [ ]).
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Shows the status of the MFDO terminals at the most recent fault where
For example, U2-13 shows
Use U1-12 [Drive Status] to monitor the actual MFDO terminal status.
bit0 : During Run
bit1 : During zero-speed
bit2 : During reverse
bit3 : During fault reset signal input
bit4 : During speed agreement
bit5 : Drive Ready
bit6 : During minor fault detection
bit7 : During fault detection
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Shows the cumulative operation time of the drive at the fault that occurred most recently.
Use U4-01 [Cumulative Ope Time] to monitor the actual cumulative operation time.
Unit: 1 h
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Shows the output frequency after soft start at the fault that occurred most recently.
Use U1-16 [SFS Output Frequency] to monitor the actual output frequency after soft start.
Unit: 0.01 Hz
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Shows the q-axis current of the motor at the fault that occurred most recently.
Use U6-01 [Iq Secondary Current] to monitor the actual q-Axis current of the motor.
Unit: 0.1 %
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Shows the d-axis current of the motor at the fault that occurred most recently.
Use U6-02 [Id ExcitationCurrent] to monitor the actual d-Axis current of the motor.
Unit: 0.1 %
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Shows the amount of control axis deviation (Δθ) at the fault that occurred most recently.
Use U6-10 [ContAxisDeviation Δθ] to monitor the actual amount of control axis deviation (Δθ).
Unit: 0.1 °
Description
= ON and
when terminals S1 and S3 are ON.
= ON and
when terminals MA and P2 are ON.
= ON and
during run.
YASKAWA SIEPC71061753A GA500 Technical Manual
MFAO Signal Level
No signal output available
= OFF.
No signal output available
= OFF.
No signal output available
= OFF.
No signal output available
No signal output available
No signal output available
No signal output available
No signal output available