YASKAWA CIPR-GA50C series Technical Manual page 691

Ac micro drives for industrial applications. 200 v class, three-phase input: 0.1 to 22 kw. 200 v class, single-phase input: 0.1 to 4.0 kw. 400 v class, three-phase input: 0.37 to 30 kw.
Table of Contents

Advertisement

0 : Stop
The drive follows the frequency reference and stops the motor.
1 : Run at (L4-06 x Last Reference)
The drive continues to operate at the frequency reference value set in L4-06 [FreqReference at Reference Loss].
When you return the external frequency reference value, the drive continues to operate with the frequency
reference.
L4-06: Frequency Reference @Loss of Ref
No.
Name
(Hex.)
L4-06
Frequency Reference
@Loss of Ref
(04C2)
Set L4-05 = 1 [FreqReference Loss Detect Select = Run@L4-06PrevRef] to enable this parameter.
L4-07: Speed Agree Detection Selection
No.
Name
(Hex.)
L4-07
Speed Agree Detection
Selection
(0470)
0 : No Detection during Baseblock
Detects the frequency while the drive is operating. When the drive turns off its output, it will not detect frequency.
1 : Detection Always Enabled
L4-08: Speed Agree Source Selection
No.
Name
(Hex.)
L4-08
Speed Agree Source
Selection
(047F)
0 : Softstarter Output (Reference)
1 : Motor Speed (Actual Speed)
The setting for L4-08 has an effect:
• When you set detection conditions for oL3 [Overtorque 1], oL3 [Overtorque Detection 1], oL4 [Overtorque 2],
and oL4 [Overtorque Detection 2]:
– L6-01 = 1, 3, 5, 7 [Torque Detection Selection 1 = UL @ Speed Agree]
– L6-04 = 1, 3, 5, 7 [Torque Detection Selection 2 = UL @ Speed Agree]
• When you use speed agreement with DriveWorksEZ.
• When the MFDI terminals set for H1-xx = 75, 76 [Up/Down 2 command] activate.
• When you set H2-xx [MFDO Function Select] to these functions:
Setting Value
2
3
4
YASKAWA SIEPC71061753A GA500 Technical Manual
Figure 12.122 Detection of Frequency Reference Loss
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the frequency reference as a percentage to continue drive operation after it detects a
frequency reference loss. The value is a percentage of the frequency reference before the drive
detected the loss.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the condition that activates speed detection.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the drive to use the soft starter output frequency or the motor speed (estimation value) for
speed detection.
Function
Speed Agree 1
User-Set Speed Agree 1
Frequency Detection 1
12.9 L: Protection Functions
Description
Description
Description
Setting Value
5
13
14
Default
(Range)
80.0%
(0.0 - 100.0%)
Default
(Range)
0
(0, 1)
Default
(Range)
1
(0, 1)
Function
Frequency Detection 2
Speed Agree 2
User-Set Speed Agree 2
691