C6: Duty & Carrier Frequency - YASKAWA CIPR-GA50C series Technical Manual

Ac micro drives for industrial applications. 200 v class, three-phase input: 0.1 to 22 kw. 200 v class, single-phase input: 0.1 to 4.0 kw. 400 v class, three-phase input: 0.37 to 30 kw.
Table of Contents

Advertisement

12.4 C: Tuning
C5-29: Speed Control Response
No.
Name
(Hex.)
C5-29
Speed Control Response
(0B18)
Expert
If a high level of speed control responsiveness is necessary, set C5-29 = 1, then adjust the speed control (ASR)
parameter.
0 : Standard
1 : High Performance 1
C5-39: ASR Primary Delay Time Const 2
No.
Name
(Hex.)
C5-39
ASR Primary Delay Time
Const 2
(030D)
If you have a load with low rigidity or if oscillation is a problem, increase this setting in 0.01 unit increments.
C6: Duty & Carrier Frequency
C6 parameters are used to set the selection of drive duty rating, selection of carrier frequency, and upper and
lower limits of carrier frequencies.
C6-01: Normal / Heavy Duty Selection
No.
Name
(Hex.)
C6-01
Normal / Heavy Duty
Selection
(0223)
0 : Heavy Duty Rating
The overload tolerance is 150% of the rated output current for 60 seconds.
1 : Normal Duty Rating
The overload tolerance is 110% of the rated output current for 60 seconds.
There are two types of load ratings for this product depending on the load characteristics of the application: Heavy
Duty Rating (HD) and Normal Duty Rating (ND).
The drive rated output current, overload tolerance, and acceleration stall prevention level change when the duty
rating changes. Set the drive to agree with the duty rating of the selected drive capacity. In HD, the tolerance is
150% overload for 60 seconds. In ND, the tolerance is 110% overload for 60 seconds. The rated output current for
ND drives is higher than the rated output current for HD drives. Refer to
V Class) on page
314,
Model-Specific Specifications (Single-Phase 200 V Class) on page
Specifications (Three-Phase 400 V Class) on page 317
Table 12.40 Differences between Heavy Duty Rating and Normal Duty Rating
Item
C6-01 Setting
Load Characteristics
536
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the level of speed control responsiveness. Usually it is not necessary to change this setting.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the filter time constant used when the torque reference is output from ASR. Usually it is not
necessary to change this parameter.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the drive duty rating.
for more information about the rated output current.
Heavy Duty Rating (HD)
0
Description
Description
Description
Model Specifications (Three-Phase 200
Normal Duty Rating (ND)
YASKAWA SIEPC71061753A GA500 Technical Manual
Default
(Range)
1
(0, 1)
Default
(Range)
0.000 s
(0.000 - 0.500 s)
Default
(Range)
0
(0, 1)
316, and
Model
1