YASKAWA CIPR-GA50C series Technical Manual page 697

Ac micro drives for industrial applications. 200 v class, three-phase input: 0.1 to 22 kw. 200 v class, single-phase input: 0.1 to 4.0 kw. 400 v class, three-phase input: 0.37 to 30 kw.
Table of Contents

Advertisement

The drive detects overtorque when the output frequency aligns with the frequency reference. Detection does not
occur during acceleration/deceleration. The drive outputs an oL3 [Overtorque Detection 1] and operation
continues.
2 : oL @ RUN - Alarm only
When the Run command is enabled, the drive constantly detects overtorque. The drive outputs an oL3 and
operation continues.
3 : oL @ Speed Agree - Fault
The drive detects overtorque when the output frequency aligns with the frequency reference. Detection does not
occur during acceleration/deceleration. The drive outputs an oL3 [Overtorque Detection 1] and operation stops.
4 : oL @ RUN - Fault
When the Run command is enabled, the drive constantly detects overtorque. The drive outputs an oL3 and
operation stops.
5 : UL @ Speed Agree - Alarm only
The drive detects undertorque when the output frequency aligns with the frequency reference. Detection does not
occur during acceleration/deceleration. The drive outputs a UL3 [Undertorque Detection 1] and operation
continues.
6 : UL @ RUN - Alarm only
When the Run command is enabled, the drive constantly detects undertorque. The drive outputs a UL3 and
operation continues.
7 : UL @ Speed Agree - Fault
The drive detects undertorque when the output frequency aligns with the frequency reference. Detection does not
occur during acceleration/deceleration. The drive outputs a UL3 and operation stops.
8 : UL @ RUN - Fault
When the Run command is enabled, the drive constantly detects undertorque. The drive outputs a UL3 and
operation stops
L6-02: Torque Detection Level 1
No.
Name
(Hex.)
L6-02
Torque Detection Level 1
(04A2)
Note:
• Set the torque detection level as a percentage of the drive rated output current in all control methods to set the mechanical weakening
detection level.
• You can also use an analog input terminal to supply the torque detection level. To enable this function, set H3-xx = 7 [MFAI Function
Select = Overtorque/Undertorque DetectLvl]. If you set L6-02 and H3-x = 7, the analog input is most important and the drive disables
L6-02.
L6-03: Torque Detection Time 1
No.
Name
(Hex.)
L6-03
Torque Detection Time 1
(04A3)
L6-04: Torque Detection Selection 2
No.
Name
(Hex.)
L6-04
Torque Detection Selection
2
(04A4)
The drive detects overtorque if the motor current or output torque is more than the level set in L6-05 [Torque
Detection Level 2] for the length of time set in L6-06 [Torque Detection Time 2]. The drive detects undertorque if
the motor current or output torque is less than the level set in L6-05 for the length the time set in L6-06.
0 : Disabled
The drive will not detect overtorque or undertorque.
YASKAWA SIEPC71061753A GA500 Technical Manual
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the detection level for Overtorque/Undertorque Detection 1. In V/f control, drive rated output
current = 100% value. In vector control, motor rated torque = 100% value.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the detection time for Overtorque/Undertorque Detection 1.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the speed range that detects overtorque and undertorque and the operation of drives
(operation status) after detection.
12.9 L: Protection Functions
Description
Description
Description
Default
(Range)
150%
(0 - 300%)
Default
(Range)
0.1 s
(0.0 - 10.0 s)
Default
(Range)
0
(0 - 8)
12
697