12.5 d: References
d4-08: Up/Down 2 Bias Upper Limit
No.
Name
(Hex.)
d4-08
Up/Down 2 Bias Upper
Limit
(02AF)
RUN
The drive saves the set bias upper limit in d4-06 [Frequency Ref Bias (Up/Down 2)]. Set d4-08 an applicable
value before you use the Up/Down 2 function.
Note:
When d4-01 = 1 [Freq Reference Hold Selection = Enabled] and b1-01 = 0 [Frequency Reference Selection 1 = Keypad], the drive will
add the bias value to the frequency reference when it does not receive an Up/Down 2 command for 5 s. Then the drive will reset the
value to 0 at which time you can increase the bias to the limit set in d4-08 again.
d4-09: Up/Down 2 Bias Lower Limit
No.
Name
(Hex.)
d4-09
Up/Down 2 Bias Lower
Limit
(02B0)
RUN
The drive saves the set bias lower limit in d4-06 [Frequency Ref Bias (Up/Down 2)]. Set d4-09 to an applicable
value before you use the Up/Down 2 function.
Note:
When d4-01 = 1 [Freq Reference Hold Selection = Enabled] and b1-01 = 0 [Frequency Reference Selection 1 = Keypad], the drive will
add the bias value to the frequency reference when it does not receive an Up/Down 2 command for 5 s. Then the drive will reset the
value to 0.
If you increase the bias with the Up 2 command and d4-09 = 0, you cannot use a Down 2 command to decrease the frequency reference.
To decrease speed in this condition, set a negative lower limit in d4-09.
d4-10: Up/Down Freq Lower Limit Select
No.
Name
(Hex.)
d4-10
Up/Down Freq Lower Limit
Select
(02B6)
0 : Greater of d2-02 or Analog
The higher value between d2-02 [Frequency Reference Lower Limit] and an analog input programmed for
Frequency Reference [H3-02, H3-10 = 0] sets the lower frequency reference limit.
Note:
When you use External Reference 1/2 Selection [H1-xx = 2] to switch between the Up/Down function and an analog input as the
reference source, the analog value becomes the lower reference limit when the Up/Down command is active. Set d4-10 = 1 to isolate the
Up/Down function and the analog input value.
1 : d2-02
You can only use d2-02 to set the lower limit of the frequency reference.
d4-11: Bi-directional Output Selection
No.
Name
(Hex.)
d4-11
Bi-directional Output
Selection
(02B7)
0 : Disabled
The drive will not change the frequency reference or PID output value to Bi-Directional internal frequency
reference.
When the frequency reference or PID output value is 0% to 100% of the maximum output frequency, the drive
runs the motor in the set direction.
1 : Enabled
Changes the frequency reference or PID output value to Bi-Directional output.
552
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the upper limit of the Up/Down 2 bias as a percentage of the Maximum Output Frequency.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the lower limit of the Up/Down 2 bias as a percentage of the Maximum Output Frequency.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the lower frequency limit for the Up/Down function.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the function that changes the frequency reference to a Bi-Directional internal frequency
reference.
Description
Description
Description
Description
YASKAWA SIEPC71061753A GA500 Technical Manual
Default
(Range)
100.0%
(0.0 - 100.0%)
Default
(Range)
0.0%
(-99.9 - 0.0%)
Default
(Range)
0
(0, 1)
Default
(Range)
0
(0, 1)