o4 parameters set the expected service life to help you know when to replace parts. The drive will show an alarm
to tell you when the replacement part interval is near.
o4-01: Elapsed Operating Time Setting
No.
Name
(Hex.)
o4-01
Elapsed Operating Time
Setting
(050B)
When you select o4-01 on the keypad, it will show the current value of U4-01 in units of 10 hours (h). When you
change the setting of o4-01 through the monitor, the U4-01 count starts again as specified by the setting of o4-01.
Note:
Set this parameter in 10-hour (h) units. When o4-01 = 30, U4-01 [Cumulative Ope Time] = 300 h.
o4-02: Elapsed Operating Time Selection
No.
Name
(Hex.)
o4-02
Elapsed Operating Time
Selection
(050C)
0 : U4-01 Shows Total Power-up Time
Counts the time from when the drive is energized to when it is de-energized.
1 : U4-01 Shows Total RUN Time
Counts the time that the drive outputs voltage.
o4-03: Fan Operation Time Setting
No.
Name
(Hex.)
o4-03
Fan Operation Time Setting
(050E)
Use monitor U4-03 [Cooling Fan Ope Time] to view the total operation time of the cooling fan. When you
replace a cooling fan, set o4-03 = 0 to reset U4-03. Select o4-03 on the keypad to show the current value of U4-03
in 10-hour (h) units. If you use the monitor to change o4-03, the recount of U4-03 starts with the o4-03 setting.
Note:
The drive sets o4-03 in 10-hour (h) units. When o4-03 = 30, U4-03 [Cooling Fan Ope Time] will show "300 h".
o4-05: Capacitor Maintenance Setting
No.
Name
(Hex.)
o4-05
Capacitor Maintenance
Setting
(051D)
When you replace a drive, set o4-05 = 0 to reset U4-05. When the o4-05 setting changes, the count of U4-05
starts again as specified by the setting of o4-05. After you complete the configuration, o4-05 automatically resets
to 0.
Note:
The maintenance period changes for different operating environments.
742
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the initial value of the cumulative drive operation time in 10-hour units.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the condition that counts the cumulative operation time.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the value from which to start the cumulative drive cooling fan operation time in 10-hour
units.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the U4-05 [CapacitorMaintenance] monitor value.
Description
Description
Description
Description
YASKAWA SIEPC71061753A GA500 Technical Manual
Default
(Range)
0 h
(0 - 9999 h)
Default
(Range)
0
(0, 1)
Default
(Range)
0 h
(0 - 9999 h)
Default
(Range)
0%
(0 - 150%)