5.3

UL Standards

The UL/cUL Mark indicates that this product satisfies stringent safety standards. This mark appears on products
in the United States and Canada. It shows UL approval, indicating that it has been determined that the product
complies with safety standards after undergoing strict inspection and assessment.
You must use UL Listed or UL Recognized parts for all primary components that are built into electrical
equipment that has UL approval.
This product has been tested in accordance with UL standard UL61800-5-1, and has been verified to be in
compliance with UL standards.
Machines and devices integrated with this product must satisfy the following conditions for compliance with UL
standards.

Area of Use

Install this product in a location with Overvoltage Category III and pollution degree 2 or less as specified in
UL61800-5-1.
Ambient Temperature Setting
Maintain the ambient temperature within the following ranges according to the enclosure type.
• IP20/UL Type 1: -10 °C to +40 °C (14 °F to 104 °F)
• IP20/UL Open Type: -10 °C to +50 °C (14 °F to 122 °F)

Wire the Main Circuit Terminal Block

Wire the main circuit terminal block correctly as specified by the instructions in the manual.
To select the correct wire gauge, refer to
Notes on Wiring the Main Circuit Terminal Block
Read these notes before you wire the main circuit terminal block.
• Use UL-Listed, vinyl-coated insulated copper wires for operation with a continuous maximum permitted
temperature of 75 °C at 600 V.
• Remove all unwanted objects that are near the terminal block connections.
• Remove the insulation from the connection wires to the wire stripping lengths shown in the manual.
• Do not use bent or crushed wires. Remove the damaged end of the wire before you use it. Incorrect connections
can cause death or serious injury from fire.
• Do not solder stranded wire. Soldered wire connections can become loose over time and cause unsatisfactory
drive performance.
• If you use stranded wire, make sure that all of the wire strands are in the connection. Also, do not twist the
stranded wire too much. Incorrect connections can cause death or serious injury from fire.
• Put the wire all the way into the terminal block. Remove the insulation from the wire to the recommended wire
stripping length to fit the wire with insulation in the plastic housing.
• Use a torque driver, torque ratchet, or torque wrench for the screws. A slotted driver or a hex tool will be
necessary to wire the screw clamp terminal. Use applicable tools as specified by the recommended conditions in
the product manual.
• If you use power tools to tighten the terminal screws, use a low speed setting (300 to 400 r/min). Failure to obey
can cause damage to the terminal screws.
• Wire gauges on existing drive models to be replaced may not match wire gauge ranges on new drives. Refer to
the drive manuals for correct wire sizes.
• Do not tighten the terminal screws at an angle of 5 degrees or more. Failure to obey can cause damage to the
terminal screws.
YASKAWA SIEPC71061753A GA500 Technical Manual
Figure 5.14 UL/cUL Mark
Main Circuit Wire Gauges and Tightening Torques on page

5.3 UL Standards

180.
5
179