5.2 European Standards
Note:
• Use a braided shield cable for the drive and motor wiring or put the wires through a metal conduit.
• Keep the wire as short as possible. The maximum wiring length between the drive and motor is:
–2xxxA, BxxxA, 4xxxA: 10 m (32.8 ft)
• Keep the grounding wire as short as possible.
4.
Use a cable clamp to ground the motor cable to the metal plate.
Note:
Make sure that the protective ground wire complies with technical specifications or local safety standards.
A - Braided shield cable
B - Metal plate
A - Grounding surface (Remove any
paint or sealant.)
B - Enclosure panel
C - Metal plate
D - Drive
E - Ground the shield.
176
Figure 5.12 Ground the shield
Figure 5.13 EMC Noise Filter and Drive Installation Procedure
C - Cable clamp (conductive)
F - Motor
G - Motor cable (Braided shield
cable: 10 m (32.8 ft) maximum)
H - Cable clamp
I - Grounding wire
J - EMC noise filter
YASKAWA SIEPC71061753A GA500 Technical Manual