YASKAWA CIPR-GA50C series Technical Manual page 418

Ac micro drives for industrial applications. 200 v class, three-phase input: 0.1 to 22 kw. 200 v class, single-phase input: 0.1 to 4.0 kw. 400 v class, three-phase input: 0.37 to 30 kw.
Table of Contents

Advertisement

11.17 U: Monitors
No.
Name
(Hex.)
U4-03
Cooling Fan Ope Time
(0067)
U4-04
Cool Fan Maintenance
(007E)
U4-05
CapacitorMaintenance
(007C)
U4-06
PreChargeRelayMainte
(07D6)
U4-07
IGBT Maintenance
(07D7)
U4-08
Heatsink Temperature
(0068)
U4-09
LED Check
(005E)
U4-10
kWh, Lower 4 Digits
(005C)
U4-11
kWh, Upper 5 Digits
(005D)
418
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Shows the cumulative operation time of the cooling fans.
Use parameter o4-03 [Fan Operation Time Setting] to reset this monitor. The maximum value that
the monitor will show is 99999. After this value is more than 99999, the drive automatically resets
it and starts to count from 0 again.
Unit: 1 h
Note:
The MEMOBUS/Modbus communication data is shown in 10 h units. Use register 009BH for
data in 1 h units.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Shows the cumulative operation time of the cooling fans as a percentage of the replacement life of
the cooling fans.
Use parameter o4-03 [Fan Operation Time Setting] to reset this monitor.
Unit: 1%
Note:
Replace the cooling fans when this monitor is 90%.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Shows the operation time of the electrolytic capacitors for the main circuit and control circuit as a
percentage of the replacement life of the electrolytic capacitors.
Use parameter o4-05 [Capacitor Maintenance Setting] to reset this monitor.
Unit: 1%
Note:
Replace the electrolytic capacitor when this monitor is 90%.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Shows the operation time of the soft charge bypass relay as a percentage of the replacement life of
the soft charge bypass relay.
Use parameter o4-07 [Softcharge Relay Maintenance Set] to reset this monitor.
Unit: 1%
Note:
Replace the drive when this monitor is 90%.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Shows the operation time of the IGBTs as a percentage of the replacement life of the IGBTs.
Set parameter o4-09 [IGBT Maintenance Setting] to reset this monitor.
Unit: 1%
Note:
Replace the drive when this monitor is 90%.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Shows the heatsink temperature of the drive.
Unit: 1 °C
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Turns on all of the keypad LEDs to make sure that the LEDs operate correctly.
1.
With U4-09 displayed, press
All LEDs on the keypad will turn on.
Note:
When Safety input 2 CH is open (STo), READY will flash.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Displays the lower 4 digits of the watt hour value for the drive.
Unit: 1 kWh
Note:
The watt hour is displayed in 9 digits. Monitor U4-11 [kWh, Upper 5 Digits] shows the upper
5 digits and U4-10 shows the lower 4 digits.
Example for 12345678.9 kWh:
U4-10: 678.9 kWh
U4-11: 12345 MWh
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Shows the upper 5 digits of the watt hour value for the drive.
Unit: 1 MWh
Note:
Monitor U4-11 shows the upper 5 digits and U4-10 [kWh, Lower 4 Digits] shows the lower 4
digits.
Example for 12345678.9 kWh:
U4-10: 678.9 kWh
U4-11: 12345 MWh
Description
.
YASKAWA SIEPC71061753A GA500 Technical Manual
MFAO Signal Level
10 V: 99999 h
10 V: 100%
10 V: 100%
10 V: 100%
10 V: 100%
10 V: 100 °C
No signal output available
No signal output available
No signal output available