YASKAWA CIPR-GA50C series Technical Manual page 253

Ac micro drives for industrial applications. 200 v class, three-phase input: 0.1 to 22 kw. 200 v class, single-phase input: 0.1 to 4.0 kw. 400 v class, three-phase input: 0.37 to 30 kw.
Table of Contents

Advertisement

Code
Name
Note:
• When H3-02 or H3-10 = E [MFAI Function Select = Motor Temperature (PTC Input)], the drive detects this fault if the motor overheat signal input from analog input
terminal A1 or A2 is more than the alarm detection level.
• Do a Fault Reset to clear the fault.
• If the drive detects this fault, it will operate the motor as specified by the Stopping Method set in L1-03 [Motor Thermistor oH Alarm Select].
Code
Name
oH4
Motor Overheat Fault (PTC Input)
Note:
• The drive detects this fault if the motor overheat signal in analog input terminals A1, or A2 is more than the Fault detection level. (If H3-02, H3-10= E [Terminal A1/A2
Function Select = Motor Temperature (PTC Input)].)
• Do a Fault Reset to clear the fault.
Code
Name
oL1
Motor Overload
YASKAWA SIEPC71061753A GA500 Technical Manual
Causes
The motor has overheated.
Causes
The motor has overheated.
Causes
The load is too large.
The acceleration/deceleration times or cycle times
are too short.
Overload occurred while running at low speed.
L1-01 [Motor Overload (oL1) Protection] is set
incorrectly.
The V/f pattern does not fit the motor qualities.
E1-06 [Base Frequency] is set incorrectly.
One drive is operating more than one motor.
The electronic thermal protector qualities and the
motor overload properties do not match.
The electronic thermal protector is operating at an
incorrect level.
Possible Solutions
• Check the load level, acceleration/deceleration time, and motor
start/stop frequency (cycle time).
• Decrease the load.
• Increase the values set in C1-01 to C1-08 [Acceleration/
Deceleration Times].
• Set E2-01 [Motor Rated Current (FLA)] correctly to the value
specified by the motor nameplate.
• Make sure that the motor cooling system is operating correctly,
and repair or replace it if it is damaged.
• Adjust E1-04 to E1-10 [V/f Pattern Parameters]. For motor 2,
adjust E3-04 to E3-10. Decrease the values set in E1-08 [Mid
Point A Voltage] and E1-10 [Minimum Output Voltage].
Note:
If the values set in E1-08 and E1-10 are too low, the overload
tolerance will decrease at low speeds.
Possible Solutions
• Check the load level, acceleration/deceleration time, and motor
start/stop frequency (cycle time).
• Decrease the load.
• Increase the values set in C1-01 to C1-08 [Acceleration/
Deceleration Times].
• Set E2-01 [Motor Rated Current (FLA)] correctly to the value
specified by the motor nameplate.
• Make sure that the motor cooling system is operating correctly,
and repair or replace it if it is damaged.
• Adjust E1-04 to E1-10 [V/f Pattern Parameters]. For motor 2,
adjust E3-04 to E3-10. Decrease the values set in E1-08 [Mid
Point A Voltage] and E1-10 [Minimum Output Voltage].
Note:
If the values set in E1-08 and E1-10 are too low, the overload
tolerance will decrease at low speeds.
Possible Solutions
Decrease the load.
Note:
Reset oL1 when U4-16 [Motor oL1 Level] < 100.
• Examine the acceleration/deceleration times and the motor
start/stop frequencies (cycle times).
• Increase the values set in C1-01 to C1-08 [Acceleration/
Deceleration Times].
• Decrease the load when running at low speed.
• Increase the motor speed.
• If the motor is run frequently at low speeds, replace the motor
with a larger motor or use a drive-dedicated motor.
Note:
For general-purpose motors, overload can occur while
running at low speed when operating at below the rated
current.
Set L1-01 in as specified by the motor qualities for a drive-
dedicated motor.
• Examine the ratios between the V/f pattern frequency and
voltage. Decrease the voltage if it is too high compared to the
frequency.
• Adjust E1-04 to E1-10 [V/f Pattern Parameters]. For motor 2,
adjust E3-04 to E3-10. Decrease the values set in E1-08 [Mid
Point A Voltage] and E1-10 [Minimum Output Voltage].
Note:
If the values set in E1-08 and E1-10 are too low, the overload
tolerance will decrease at low speeds.
Set E1-06 to the rated frequency shown on the motor nameplate.
Set L1-01 = 0 [Motor Overload (oL1) Protection = Disabled],
connect thermal overload relay to each motor to prevent damage
to the motor.
• Examine the motor qualities and set L1-01 [Motor Overload
(oL1) Protection] correctly.
• Connect a thermal overload relay to the motor.
Set E2-01 [Motor Rated Current (FLA)] correctly to the value
specified by the motor nameplate.
7.4 Faults
7
253

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ga500 series

Table of Contents