NOTICE: Do not let wire shields touch other signal lines or equipment. Insulate the wire shields with electrical tape or shrink
tubing. If you do not insulate the wire shields, it can cause a short circuit and damage the drive.
Note:
• Use a Class 2 power supply to connect external power to the control terminals. If the power supply for peripheral devices is incorrect, it
can cause a decrease in drive performance.
• Connect the shield of shielded cable to the applicable ground terminal. Incorrect equipment grounding can cause drive or equipment
malfunction from electrical interference.
• Isolate wiring for contact output terminals MA, MB, MC, P1, C1, P2, and C2 from other control circuit wiring. The drive and
connected equipment will malfunction or the drive can trip because of incorrect wiring.
• Isolate control circuit wiring from main circuit wiring (terminals R/L1, S/L2, T/L3, L/L1, N/L2, B1, B2, U/T1, V/T2, W/T3, -, +1, +2)
and other high-power wiring. If control circuit wiring is adjacent to main circuit wiring, it can cause incorrect operation of the drive
and equipment from electrical interference.
Wire the grounding terminal and main circuit terminals, then wire the control circuit terminals.
1.
Remove the front cover from the drive.
To move Jumper S5, also remove the keypad.
2.
Refer to the following figure and wire the control circuit.
Use a flat bladed screwdriver with a blade width of 2 .5mm (0.1 in) or less and thickness of 0.4 mm (0.01
in) or less.
WARNING! Fire Hazard. Tighten all terminal screws to the correct tightening torque. Connections that are too loose or
too tight can cause incorrect operation and damage to the drive. Incorrect connections can also cause death or
serious injury from fire.
Note:
• Use shielded, twisted-pair wires and ground the shield to the ground terminal of the drive. Incorrect equipment grounding
can cause drive or equipment malfunction from electrical interference.
• Do not use control circuit wiring that is longer than 50 m (164 ft) to supply the analog frequency reference from a remote
source. If the control circuit wiring is too long, it can cause unsatisfactory system performance.
A - Wire with a crimp ferrule
attached, or unsoldered wire with
the core wires lightly twisted
B - Pull back the shielding and lightly
twist the end with your fingers to
keep the ends from fraying.
Note:
• Do not solder the core wire. Soldered wiring connections can become loose and cause the drive to malfunction.
• Refer to
Figure 3.39
for information to prepare terminal ends of the shielded wire.
• Prepare the wire ends of shielded twisted-pair wires as shown in
frequency setting potentiometer to set the frequency. Connect the shield to terminal E (G) of the drive.
YASKAWA SIEPC71061753A GA500 Technical Manual
Figure 3.37 Remove the Front Cover
Figure 3.38 Wiring Procedure for the Control Circuit
C - Remove approximately 5.5 mm
(0.21 in) of the covering at the end
of the wire if you do not use crimp
ferrules.
Figure 3.39
to use an analog reference from an external
3.5 Control Circuit Wiring
3
87