When terminal S1 (Run command) activates for 1 ms minimum, the drive rotates the motor. When terminal S2
(Stop command) deactivates, the drive stops. When terminal Sx that is set in 3-wire sequence deactivates, the
drive operates in the forward direction, and when it activates, the drive operates in the reverse direction.
WARNING! Sudden Movement Hazard. Set the MFDI parameters before you close control circuit switches. Incorrect Run/Stop
circuit sequence settings can cause serious injury or death from moving equipment.
WARNING! Sudden Movement Hazard. When you use a 3-Wire sequence, set A1-03 = 3330 [Initialize Parameters = 3-Wire
Initialization] and make sure that b1-17 = 0 [Run Command at Power Up = Disregard Existing RUN Command] (default). If you
do not correctly set the drive parameters for 3-Wire operation before you energize the drive, the motor can suddenly rotate in
reverse when you energize the drive.
.
Note:
• To input the Run command, activate the terminal for 1 ms minimum.
• The default setting for b1-17 [Run Command at Power Up] is 0 [Disregard existing RUN command]. If you enable the Run command
when the drive is energized, the protective function activates and the
17 = 1 [Accept Existing RUN Command].
1: LOCAL/REMOTE Selection
Setting Value
Function
1
LOCAL/REMOTE
Selection
Note:
• When the MFDI terminal sets the LOCAL/REMOTE selection,
• When LOCAL Mode is selected, the green light for
• When the Run command is ON, you cannot switch between LOCAL Mode and REMOTE Mode.
ON : LOCAL
The keypad is the Frequency reference source and Run command source.
OFF : REMOTE
The frequency reference and Run command settings are set in b1-01, b1-02 [Frequency Reference Selection 1/2]
or b1-15, b1-16 [Run Command Selection 1/2].
YASKAWA SIEPC71061753A GA500 Technical Manual
Figure 12.64 3-Wire Sequence Wiring Example
Figure 12.65 3-Wire Sequence Time Chart
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets drive control for the keypad (LOCAL) or an external source (REMOTE).
comes on.
12.8 H: Terminal Function Selection
flashes quickly. When the application allows Run, set b1-
Description
on the keypad is disabled.
12
603