12.8 H: Terminal Function Selection
Note:
• Turning ON the Forward Run command terminal and the Reverse Run command terminal will cause alarm EF [FWD/REV Run
Command Input Error] and the motor will ramp to stop.
• Initialize the drive with a 2-wire sequence to set the Reverse Run command to terminal S2.
• This function will not operate at the same time as H1-xx = 42, 43 [Run Command/FWD/REV Command (2-Wire Seq 2)].
42: Run Command (2-Wire Sequence 2)
Setting Value
Function
42
Run Command (2-Wire
Sequence 2)
ON : Run
OFF : Stop
Note:
This function will not operate at the same time as H1-xx = 40, 41 [Forward/Reverse Run Command (2-Wire Seq)].
43: FWD/REV (2-Wire Sequence 2)
Setting Value
Function
43
FWD/REV (2-Wire
Sequence 2)
ON : Reverse
OFF : Forward
Note:
• You must input the Run command to rotate the motor.
• This function will not operate at the same time as H1-xx = 40, 41 [Forward/Reverse Run Command (2-Wire Seq)].
44: Add Offset Frequency 1 (d7-01)
Setting Value
Function
44
Offset Frequency 1
Note:
Refer to "d7: Offset Frequency" for more information.
45: Add Offset Frequency 2 (d7-02)
Setting Value
Function
45
Offset Frequency 2
Note:
Refer to "d7: Offset Frequency" for more information.
46: Add Offset Frequency 3 (d7-03)
Setting Value
Function
46
Offset Frequency 3
Note:
Refer to "d7: Offset Frequency" for more information.
47: Node Setup (CANopen)
Setting Value
Function
47
Node Setup (CANopen)
614
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the Run command for 2-wire sequence 2. Set this function and H1-xx = 43 [FWD/REV Command (2-Wire Seq 2)] at the
same time.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the direction of motor rotation for 2-wire sequence 2. Set this function and H1-xx = 42 [Run Command (2-Wire Sequence
2)] together.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the function to add the offset frequency set in d7-01 [Offset Frequency 1] to the frequency reference when the terminal
activates.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the function to add the offset frequency set in d7-02 [Offset Frequency 2] to the frequency reference when the terminal
activates.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the function to add the offset frequency set in d7-03 [Offset Frequency 3] to the frequency reference when the terminal
activates.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the function in CANopen communications to start the Node Setup function to set the drive node address from the host
controller.
Description
Description
Description
Description
Description
Description