b1-17: Run Command at Power Up
No.
Name
(Hex.)
b1-17
Run Command at Power Up
(01C6)
0 : Disregard Existing RUN Command
The drive does not start to operate the application when the power is switched ON, even when there is an existing
Run command.
Enter the Run command again to operate the application.
Note:
When you energize the drive,
1 : Accept Existing RUN Command
When there is an existing Run command, the drive starts to operate the application when the power is switched
ON.
WARNING! Sudden Movement Hazard. When you use a 3-Wire sequence, set A1-03 = 3330 [Initialize Parameters = 3-Wire
Initialization] and make sure that b1-17 = 0 [Run Command at Power Up = Disregard Existing RUN Command] (default). If you
do not correctly set the drive parameters for 3-Wire operation before you energize the drive, the motor can suddenly rotate in
reverse when you energize the drive.
b1-35: Digital Input Deadband Time
No.
Name
(Hex.)
b1-35
Digital Input Deadband
Time
(1117)
Expert
When the on/off time for MFDIs is longer than the time set in b1-35, the drive activates the MFDI. Set this
parameter to prevent malfunctions caused by relay chattering for applications in which relays send input to MFDI
terminals.

b2: DC Injection Braking and Short Circuit Braking

b2 parameters set the DC Injection Braking and Short Circuit Braking functions.
• DC Injection Braking: A braking method that injects DC current into the motor windings. This function should
not be used too frequently, because it generates a fair amount of heat in the motor.
• Short Circuit Braking: A braking method for PM motors.
b2-01: DC Injection/Zero SpeedThreshold
No.
Name
(Hex.)
b2-01
DC Injection/Zero
SpeedThreshold
(0189)
Note:
This parameter is available when b1-03 = 0 [Stopping Method Selection = Ramp to Stop].
When the control method selected in A1-02 [Control Method Selection] changes, the b2-01 function changes.
486
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets drive response when energizing a drive that has an external Run command. Set this
parameter in applications where energizing or de-energizing the drive enables the Run command.
on the keypad will flash quickly if the Run command is already enabled from an external source.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the deadband time for MFDIs.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the frequency to start DC Injection Braking or Short Circuit Braking.
Description
Description
Description
YASKAWA SIEPC71061753A GA500 Technical Manual
Default
(Range)
0
(0, 1)
Default
(Range)
0.0 ms
(0.0 to 100.0 ms)
Default
(Range)
Determined by A1-02
(0.0 - 10.0 Hz)