H3: Analog Inputs - YASKAWA CIPR-GA50C series Technical Manual

Ac micro drives for industrial applications. 200 v class, three-phase input: 0.1 to 22 kw. 200 v class, single-phase input: 0.1 to 4.0 kw. 400 v class, three-phase input: 0.37 to 30 kw.
Table of Contents

Advertisement

A - H2-30
[Comparator 2 On-Delay Time]
Note:
The drive compares the monitors set with H2-26 as absolute values.
69: External Power 24V Supply
Setting Value
Function
69
External Power 24V Supply
ON : An external 24V power supply supplies power.
OFF : An external 24V power supply does not supply power.
6A: Data Logger Error
Setting Value
Function
6A
Data Logger Error
90 to 92: DWEZ Digital Output 1 to 3
Setting Value
Function
90 - 92
DWEZ Digital Output 1 to
3
100 to 192: Inverse output of 0 to 92
Setting Value
Function
100 - 192
Inverse output of 0 to 92
For example, set H2-xx = 10E for the inverse output of E [Fault].

H3: Analog Inputs

WARNING! Sudden Movement Hazard. Do test runs and examine the drive to make sure that the command references are
correct. If you set the command reference incorrectly, it can cause damage to the drive or serious injury or death.
Drives have two analog input terminals: terminals A1 and A2. Use H3 parameters to set the functions to these
analog input terminals and adjust signal levels.
Table 12.64
shows the functions that you can set to analog input terminals. Use H3-02 and H3-10 [MFAI Function
Select] to set functions.
Setting
Function
Value
0
Frequency Reference
1
Frequency Gain
YASKAWA SIEPC71061753A GA500 Technical Manual
Figure 12.89 Comparator 2 Output Time Chart
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
The terminal activates when there is an external 24V power supply between terminals PS-AC.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
The terminal activates when the drive detects LoG [Com Error / Abnormal SD card].
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the DriveWorksEZ digital output. Refer to the DriveWorksEZ online manual for more information.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Causes inverse output of the function for the selected MFDO. Uses the last two digits of 1xx to select which function to
inversely output.
Table 12.64 MFAI Setting Values
Reference
646
646
12.8 H: Terminal Function Selection
B - H2-31
[Comparator 2 Off-Delay Time]
Description
Description
Description
Description
Setting
Function
Value
2
Auxiliary Frequency Reference 1
3
Auxiliary Frequency Reference 2
Reference
647
12
647