YASKAWA CIPR-GA50C series Technical Manual page 735

Ac micro drives for industrial applications. 200 v class, three-phase input: 0.1 to 22 kw. 200 v class, single-phase input: 0.1 to 4.0 kw. 400 v class, three-phase input: 0.37 to 30 kw.
Table of Contents

Advertisement

o1-44: 2nd Monitor Area Setting
No.
Name
(Hex.)
o1-44
2nd Monitor Area Setting
(11C4)
RUN
o1-45: 3rd Monitor Area Selection
No.
Name
(Hex.)
o1-45
3rd Monitor Area Selection
(11C5)
RUN
0 : +/- Area ( - o1-46 ~ o1-46 )
1 : + Area ( 0 ~ o1-46 )
2 : - Area ( - o1-46 ~ 0 )
o1-46: 3rd Monitor Area Setting
No.
Name
(Hex.)
o1-46
3rd Monitor Area Setting
(11C6)
RUN
o1-47: Trend Plot 1 Scale Minimum Value
No.
Name
(Hex.)
o1-47
Trend Plot 1 Scale
Minimum Value
(11C7)
RUN
o1-48: Trend Plot 1 Scale Maximum Value
No.
Name
(Hex.)
o1-48
Trend Plot 1 Scale
Maximum Value
(11C8)
RUN
o1-49: Trend Plot 2 Scale Minimum Value
No.
Name
(Hex.)
o1-49
Trend Plot 2 Scale
Minimum Value
(11C9)
RUN
o1-50: Trend Plot 2 Scale Maximum Value
No.
Name
(Hex.)
o1-50
Trend Plot 2 Scale
Maximum Value
(11CA)
RUN
YASKAWA SIEPC71061753A GA500 Technical Manual
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the horizontal axis value used to display the monitor set in o1-25 [Custom Monitor 2] as a
bar graph. This parameter is only available when using an LCD keypad.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the horizontal range used to display the monitor set in o1-26 [Custom Monitor 3] as a bar
graph. This parameter is only available when using an LCD keypad.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the horizontal axis value used to display the monitor set in o1-26 [Custom Monitor 3] as a
bar graph. This parameter is only available when using an LCD keypad.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the horizontal axis minimum value used to display the monitor set in o1-24 [Custom Monitor
1] as a trend plot. This parameter is only available when using an LCD keypad.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the horizontal axis maximum value used to display the monitor set in o1-24 [Custom Monitor
1] as a trend plot. This parameter is only available when using an LCD keypad.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the horizontal axis minimum value used to display the monitor set in o1-25 [Custom Monitor
2] as a trend plot. This parameter is only available when using an LCD keypad.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the horizontal axis maximum value used to display the monitor set in o1-25 [Custom Monitor
2] as a trend plot. This parameter is only available when using an LCD keypad.
12.11 o: Keypad-Related Settings
Description
Description
Description
Description
Description
Description
Description
Default
(Range)
100.0%
(0.0 - 100.0%)
Default
(Range)
0
(0 - 2)
Default
(Range)
100.0%
(0.0 - 100.0%)
Default
(Range)
-100.0%
(-300.0 - +300.0%)
Default
(Range)
100.0%
(-300.0 - +300.0%)
Default
(Range)
-100.0%
(-300.0 - +300.0%)
Default
(Range)
100.0%
(-300.0 - +300.0%)
12
735