11.10 H: Terminal Functions
Setting Value
Function
3F
PID Setpoint Selection 2
40
Forward RUN (2-Wire)
41
Reverse RUN (2-Wire)
42
Run Command (2-Wire
Sequence 2)
43
FWD/REV (2-Wire
Sequence 2)
44
Offset Frequency 1
45
Offset Frequency 2
46
Offset Frequency 3
47
Node Setup (CANopen)
60
DC Injection Braking
Command
61
Speed Search from Fmax
62
Speed Search from Fref
63
Field Weakening
372
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Set this function and H1-xx = 3E [PID Setpoint Selection 1] at the same time. Sets the function to switch the PID
setpoint to b5-58 to b5-60 [PID Setpoint 2 to 4].
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the Forward Run command for 2-wire sequence 1. Set this function and H1-xx = 41 [Reverse Run Command
(2-Wire Seq)] at the same time.
ON : Forward Run
OFF : Run Stop
Note:
• If you activate the Forward Run command terminal and the Reverse Run command terminal, the drive will
detect minor fault/alarm EF [FWD/REV Run Command Input Error] and the motor will ramp to stop.
• Initialize the drive with a 2-wire sequence to set the Forward Run command to terminal S1.
• This function will not operate at the same time as H1-xx = 42, 43 [Run Command/FWD/REV Command (2-
Wire Seq 2)].
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the Forward Run command for 2-wire sequence 1. Set this function and H1-xx = 40 [Forward Run Command
(2-Wire Seq)] at the same time.
ON : Reverse Run
OFF : Run Stop
Note:
• If you activate the Forward Run command terminal and the Reverse Run command terminal, the drive will
detect minor fault/alarm EF [FWD/REV Run Command Input Error] and the motor will ramp to stop.
• Initialize the drive with a 2-wire sequence to set the Reverse Run command to terminal S2.
• This function will not operate at the same time as H1-xx = 42, 43 [Run Command/FWD/REV Command (2-
Wire Seq 2)].
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the Run command for 2-wire sequence 2. Set this function and H1-xx = 43 [FWD/REV Command (2-Wire Seq
2)] at the same time.
ON : Run
OFF : Stop
Note:
This function will not operate at the same time as H1-xx = 40, 41 [Forward/Reverse Run Command (2-Wire
Seq)].
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the direction of motor rotation for 2-wire sequence 2. Set this function and H1-xx = 42 [Run Command (2-
Wire Sequence 2)] together.
ON : Reverse run
OFF : Forward run
Note:
This function will not operate at the same time as H1-xx = 40, 41 [Forward/Reverse Run Command (2-Wire
Seq)].
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the function to add the offset frequency set in d7-01 [Offset Frequency 1] to the frequency reference when the
terminal activates.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the function to add the offset frequency set in d7-02 [Offset Frequency 2] to the frequency reference when the
terminal activates.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the function to add the offset frequency set in d7-03 [Offset Frequency 3] to the frequency reference when the
terminal activates.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the function in CANopen communications to start the Node Setup function to set the drive node address from
the host controller.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the command to use DC Injection Braking to stop the motor.
Note:
When A1-02 = 8 [Control Method Selection = EZOLV], this function is available only when you use a PM
motor.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the function to start speed search using an external reference although b3-01 = 0 [Speed Search Selection at
Start = Disabled].
Note:
The drive will detect oPE03 [Multi-Function Input Setting Err] when H1-xx = 61 and 62 are set at the same
time.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the function to use an external reference to start speed search although b3-01 = 0 [Speed Search Selection at
Start = Disabled].
Note:
The drive will detect oPE03 [Multi-Function Input Setting Err] when H1-xx = 61 and 62 are set at the same
time.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the function to send the Field Weakening Level and Field Weakening Frequency Limit commands set in d6-
01[Field Weakening Level] and d6-02 [Field Weakening Frequency Limit] when the input terminal is activated.
Description
YASKAWA SIEPC71061753A GA500 Technical Manual