L3: Stall Prevention - YASKAWA CIPR-GA50C series Technical Manual

Ac micro drives for industrial applications. 200 v class, three-phase input: 0.1 to 22 kw. 200 v class, single-phase input: 0.1 to 4.0 kw. 400 v class, three-phase input: 0.37 to 30 kw.
Table of Contents

Advertisement

12.9 L: Protection Functions
Note:
• If the drive detects Uv1 [DC Bus Undervoltage] during KEB operation, decrease the value of C1-09.
• If the drive detects ov [Overvoltage] during KEB operation, increase the value of C1-09.
1 : Single Drive KEB Ride-Thru 2
The drive does KEB operation and automatically calculates the deceleration rate to make sure that the main circuit
electrical energy and main current voltage from motor regenerative energy is equal to L2-11 [DC Bus Vol Setpoint
during KEB].
2 : System KEB Ride-Thru 1
The drive does not monitor the DC bus voltage and decelerates as specified by the KEB deceleration time set in
L2-06.
Set L2-06 to the time necessary to decelerate from the frequency reference to 0 Hz when the drive detects a
momentary power loss. The drive can decelerate and keep constant deceleration rates for more than one drive.
Note:
If you keep constant deceleration rates for more than one drive, it can trigger ov faults. Use the dynamic braking option with System
KEB Ride-Thru 1 to prevent ov faults.
3 : System KEB Ride-Thru 2
The drive monitors the DC bus voltage and decelerates for the deceleration time set in L2-06.
If the DC bus voltage increases, the drive momentarily holds the frequency to prevent ov while deceleration
continues.
Note:
When you cannot use a dynamic braking option, use System KEB Ride-Thru.
L2-30: KEB Zero Speed Operation
No.
Name
(Hex.)
L2-30
KEB Zero Speed Operation
(045E)
Expert
0 : Baseblock
1 : DC/SC Braking
Does DC injection braking and short circuit braking as specified by b2-04 [DC Inject Braking Time at Stop] and
b2-13 [Short Circuit Brake Time @ Stop].
L2-31: KEB Start Voltage Offset Level
No.
Name
(Hex.)
L2-31
KEB Start Voltage Offset
Level
(045D)
Expert
The drive uses this formula to calculate the KEB start voltage:
KEB start voltage = L2-05 [Undervoltage Detect Level (Uv1)] + L2-31

L3: Stall Prevention

L3 parameters set the Stall Prevention function and overvoltage suppression function.
Stall Prevention
If the load is too heavy or the acceleration and deceleration times are too short, the motor can slip too much
because it cannot work at the same rate as the frequency reference. If the motor stalls during acceleration, current
increases as the slip increases to cause an oC [Overcurrent], oL2 [Drive Overload], or oL1 [Motor Overload] and
the drive will stop. If the motor stalls during deceleration, too much regenerative power will flow back into the
DC bus capacitors, and cause the drive to fault out from ov [Overvoltage] and the drive will stop.
The stall prevention function will let the motor get to the set speed without stalling and it is not necessary for you
to change the acceleration or deceleration time settings. You can set a separate stall prevention functions for
acceleration, operating at constant speeds, and deceleration.
680
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the operation when the output frequency decreases below the zero level (DC braking
injection starting frequency) during KEB deceleration when L2-01 = 3 to 5 [Power Loss Ride
Through Select = Kinetic Energy Backup: L2-02, Kinetic Energy Backup: CPU Power, or Kinetic
Energy Backup: DecelStop].
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the KEB start voltage offset.
Description
Description
YASKAWA SIEPC71061753A GA500 Technical Manual
Default
(Range)
0
(0, 1)
Default
(Range)
Determined by A1-02
(200 V Class: 0 - 100 V,400
V Class: 0 - 200 V)