12.8 H: Terminal Function Selection
2: External Reference 1/2 Selection
Setting Value
Function
2
External Reference 1/2
Selection
Note:
When the drive is receiving a Run command, you cannot switch between reference sources.
ON : b1-15 = [Frequency Reference Selection 2], b1-16 [Run Command Selection 2]
OFF : b1-01 = [Frequency Reference Selection 1], b1-02 [Run Command Selection 1]
3: Multi-Step Speed Reference 1
Setting Value
Function
3
Multi-Step Speed Reference
1
Note:
Refer to "Setting Procedures for Multi-step Speed Operation" in "d: Reference Settings" for more information.
4: Multi-Step Speed Reference 2
Setting Value
Function
4
Multi-Step Speed Reference
2
Note:
Refer to "Setting Procedures for Multi-step Speed Operation" in "d: Reference Settings" for more information.
5: Multi-Step Speed Reference 3
Setting Value
Function
5
Multi-Step Speed Reference
3
Note:
Refer to "Setting Procedures for Multi-step Speed Operation" in "d: Reference Settings" for more information.
6: Jog Reference Selection
Setting Value
Function
6
Jog Reference Selection
7: Accel/Decel Time Selection 1
Setting Value
Function
7
Accel/Decel Time Selection
1
Note:
Refer to "C1: Accel & Decel Time" for more information.
8: Baseblock Command (N.O.)
Setting Value
Function
8
Baseblock Command
(N.O.)
The keypad flashes bb [Baseblock]. If you cancel the baseblock command when the Run command is active, the
drive will restart the motor and use the speed search function.
WARNING! Sudden Movement Hazard. When you use a mechanical holding brake with the drive in a lifting application, you
must close the brake if an input terminal triggers the Baseblock command to stop drive output. If you enter the baseblock
command, the motor will suddenly coast and the load will slip, which can cause serious injury or death.
604
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the drive to use Run command source 1/2 or Reference command source 1/2 when in REMOTE Mode.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Uses speed references d1-01 to d1-16 to set a multi-step speed reference.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Uses speed references d1-01 to d1-16 to set a multi-step speed reference.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Uses speed references d1-01 to d1-16 to set a multi-step speed reference.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the drive to use the JOG Frequency Reference (JOG command) set in d1-17. The JOG Frequency Reference (JOG
command) overrides Frequency References 1 to 16 (d1-01 to d1-16).
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the drive to use Acceleration/Deceleration Time 1 [C1-01, C1-02] or Acceleration/Deceleration Time 2 [C1-03, C1-04].
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the command that stops drive output and coasts the motor to stop when the input is ON.
Description
Description
Description
Description
Description
Description
Description