3 : Option PCB
Use a communications option card connected to the drive to enter the Run command.
Refer to the instruction manual included with the option card to install and set the option card.
Note:
If you set b1-15 = 3 but you do not connect an option card, oPE03 [Multi-Function Input Setting Err] will flash on the keypad.
4 : Pulse Train Input
Use a pulse train signal from the pulse train input terminal RP to enter the frequency reference.
Do this procedure to make sure that the pulse train signal is operating correctly.
1. Set b1-15 = 4, H6-01 = 0 [Terminal RP Pulse Train Function = Frequency Reference].
2. Set H6-02 [Terminal RP Frequency Scaling] to the number of pulses that determine 100% of the frequency
reference.
3. The terminal set in H1-xx = 2 [MFDI Function Selection = External Reference 1/2 Selection] is activated.
4. Enter a pulse train signal on the terminal RP and make sure that the keypad shows a correct frequency
reference.
b1-16: Run Command Selection 2
No.
Name
(Hex.)
b1-16
Run Command Selection 2
(01C5)
Activate H1-xx = 2 [MFDI Function Selection = External Reference 1/2 Selection] to enable this parameter.
0 : Keypad
Use the keypad to enter the Run command.
You can use the JOG operation or the FWD/REV commands from the keypad.
Note:
The
is on while the keypad is the Run command source.
1 : Digital Input
Use the control circuit terminals to enter the Run command. Select the input method for the Run command with
an H1-xx parameter.
Set H1-xx = 0, 40 to 43 [3-Wire Sequence, Run Command (2-Wire Sequence)]. The default setting is 2-wire
sequence 1.
• 2-wire Sequence 1
This sequence has two input types: FWD/Stop and REV/Stop. Set A1-03 = 2220 [Initialize Parameters = 2-
Wire Initialization] to initialize the drive and set terminals S1 and S2 for a 2-wire sequence.
• 2-wire Sequence 2
This sequence has two input types: Run/Stop and FWD/REV.
• 3-Wire Sequence
This sequence has three input types: Run, Stop, and FWD/REV. Set A1-03 = 3330 [Initialize Parameters = 3-
Wire Initialization] to initialize the drive and set terminals S1, S2, and S5 for a 3-wire sequence.
2 : Memobus/Modbus Communications
Use MEMOBUS/Modbus communications to enter the Run command.
3 : Option PCB
Use a communications option card or input option card connected to the drive to enter the Run command.
Refer to the instruction manual included with the option card to install and set the option card.
Note:
If b1-16 = 3 but no option card is connected, then oPE03 [Multi-Function Input Setting Err] will flash on the keypad.
YASKAWA SIEPC71061753A GA500 Technical Manual
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the input method for Run Command 2 when the user switches the control circuit terminals
ON/OFF to change the Run command source.
Description
12.3 b: Application
Default
(Range)
0
(0 - 3)
12
485