YASKAWA CIPR-GA50C series Technical Manual page 459

Ac micro drives for industrial applications. 200 v class, three-phase input: 0.1 to 22 kw. 200 v class, single-phase input: 0.1 to 4.0 kw. 400 v class, three-phase input: 0.37 to 30 kw.
Table of Contents

Advertisement

A1-03: Initialize Parameters
No.
Name
(Hex.)
A1-03
Initialize Parameters
(0103)
Note:
• After you initialize the drive, the drive automatically sets A1-03 = 0.
• User Parameters can save the parameter values for your application and use these values as default values for drive initialization.
• To use the 2 motor switchover function, first turn OFF the terminal to which H1-xx = 16 [MFDI Function Selection = Motor 2
Selection] is set, then change the A1-03 setting. An incorrect procedure will trigger oPE08 [Parameter Selection Error].
0 : No Initialization
1110 : User Initialization
Sets parameters to the values set by the user as user settings. Set o2-03 = 1 [User Parameter Default Value = Set
defaults] to save the user settings.
You can save the parameter settings that were adjusted for the test run as user-set default values to the drive.
When you make changes to the parameter values after you save the settings as User Parameter Settings, the drive
will set the parameters to the User Parameter Setting value when you initialize with A1-03 = 1110.
Follow this procedure to save User Parameter setting values, and to do a User Initialization.
1. Set parameters correctly for the application.
2. Set o2-03 = 1 [User Parameter Default Value = Set defaults].
This saves parameter settings for a User Initialization.
The drive will then automatically set o2-03 = 0.
3. Set A1-03 = 1110 to reset to the saved parameter settings.
When you initialize the drive, the drive sets the parameter values to the User Parameter setting values.
2220 : 2-Wire Initialization
Sets MFDI terminal S1 to Forward Run and terminal S2 to Reverse Run, and resets all parameters to default
settings.
3330 : 3-Wire Initialization
Sets MFDI terminal S1 to Run, terminal S2 to Stop, and terminal S5 to FWD/REV, and resets all parameters to
default settings.
The drive will not initialize the parameters in
Table 12.2 Parameters that are not Initialized Using a 2-Wire Sequence or a 3-Wire Sequence
No.
A1-00
A1-02
A1-07
E1-03
E5-01
E5-02
E5-03
E5-04
E5-05
E5-06
E5-07
E5-09
E5-24
E5-25
F6-08
F6-xx/F7-xx
L8-35
YASKAWA SIEPC71061753A GA500 Technical Manual
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets parameters to default values.
Table 12.2
when A1-03 = 2220, 3330.
Language Selection
Control Method Selection
DriveWorksEZ Function Selection
V/f Pattern Selection
PM Motor Code Selection
PM Motor Rated Power (kW)
Motor Rated Current (FLA)
PM Motor Pole Count
PM Motor Resistance (ohms/phase)
PM d-axis Inductance (mH/phase)
PM q-axis Inductance (mH/phase)
PM Back-EMF Vpeak (mV/(rad/s))
PM Back-EMF L-L Vrms (mV/rpm)
Polarity Estimation Timeout
Comm Parameter Reset @Initialize
Communication Option Parameters
Set F6-08 = 1 [Comm Parameter Reset @Initialize = Reset Back to Factory Default] to initialize communication option
parameters.
Installation Method Selection
12.2 A: Initialization Parameters
Description
Name
Default
(Range)
0
(0 - 3330)
12
459