7.6 Parameter Setting Errors
Code
Name
Code
Name
oPE05
Run Cmd/Freq Ref Source Sel Err
Code
Name
oPE07
Analog Input Selection Error
270
Causes
Settings for N.C. and N.O. input [H1-xx] for these
functions were selected at the same time:
• Setting value 15 [Fast Stop (N.O.)]
• Setting value 17 [Fast Stop (N.C.)]
These settings were entered while H1-xx = 2
[External Reference 1/2 Selection]:
• b1-15 = 4 [Frequency Reference Selection 2 =
Pulse Train Input]
• H6-01 ≠ 0 [Terminal RP Pulse Train Function ≠
Frequency Reference]
These settings were entered while H1-xx = 2
[External Reference 1/2 Selection]:
• b1-15 = 3 [Option PCB] or b1-16 = 3 [Run
Command Selection 2 = Option PCB]
• No option is connected to the drive.
These settings were entered while H1-xx = 2
[External Reference 1/2 Selection]:
• b1-15 = 1 [Analog Input]
• H3-02 ≠ 0 [Terminal A1 Function Selection ≠
Frequency Reference] or H3-10 ≠ 0 [Terminal
A2 Function Selection ≠ Frequency Reference]
These parameters are set at the same time:
• H1-xx ≠ 6A [Drive Enable]
• H2-xx = 38 [Drive Enabled]
These parameters are set at the same time:
• H6-01 ≠ 3 [PG Speed Feedback (V/F Control)]
• H1-xx = 7E [Reverse Rotation Identifier]
These parameters are set at the same time:
• H1-xx = 75/76 [Up 2 /Down 2 Command]
• H3-01, H3-09 = 1 [Terminal A1, A2 Signal
Level Select = 0 to +10V(Without Limit)]
Causes
The setting to assign the Run command or
frequency reference to an option card or the pulse
train input is incorrect.
b1-01 = 3 [Frequency Reference Selection 1 =
Option PCB] is set, but there is no option card
connected to the drive.
b1-02 = 3 [Run Command Selection 1 = Option
PCB] is set, but there is no option card connected to
the drive.
These parameters are set at the same time:
• b1-01 = 4 [Pulse Train Input]
• H6-01 ≠ 0 [Terminal RP Pulse Train Function ≠
Frequency Reference]
Causes
The settings for H3-02 and H3-10 [MFAI Function
Select] and H7-30 [Virtual Analog Input Selection]
overlap.
These parameters are set at the same time:
• H3-02, H3-10, H7-30 = B [PID Feedback]
• H6-01 = 1 [Terminal RP Pulse Train Function =
PID Feedback Value]
These parameters are set at the same time:
• H3-02, H3-10, H7-30 = C [PID Setpoint]
• H6-01 = 2 [PID Setpoint Value]
These parameters are set at the same time:
• H3-02, H3-10, H7-30 = C
• b5-18 = 1 [PID Setpoint Selection = Enabled]
These parameters are set at the same time:
• H6-01 = 2
• b5-18 = 1
Possible Solutions
Remove one of the function settings.
Set H6-01 = 0.
Connect an input option to the drive.
Set H3-02 = 0 or H3-10 = 0.
Correct the parameter settings.
Correct the parameter settings.
Remove one of the function settings.
Possible Solutions
Correct the parameter settings.
Connect an option card to the drive.
Set H6-01 = 0.
Possible Solutions
Set H3-02, H3-10, and H7-30 correctly to prevent overlap.
Note:
It is possible to set these functions to multiple analog input
terminals at the same time:
• Setting value 0 [Frequency Reference]
• Setting values F and 1F [Not Used]
Remove the function settings that are not in use.
YASKAWA SIEPC71061753A GA500 Technical Manual