YASKAWA CIPR-GA50C series Technical Manual page 747

Ac micro drives for industrial applications. 200 v class, three-phase input: 0.1 to 22 kw. 200 v class, single-phase input: 0.1 to 4.0 kw. 400 v class, three-phase input: 0.37 to 30 kw.
Table of Contents

Advertisement

No.
Item
3
Time stamp
4
Log Monitor Data 1
5
Log Monitor Data 2
:
:
13
Log Monitor Data 10
14
Reserved
15
Encoding data
16
Row number
o5-01: Log Start/Stop Selection
No.
Name
(Hex.)
o5-01
Log Start/Stop Selection
(1551)
RUN
0 : OFF
Stops the data log.
1 : ON
Starts the data log as specified by the sampling cycle set in o5-02 [Log Sampling Interval].
o5-02: Log Sampling Interval
No.
Name
(Hex.)
o5-02
Log Sampling Interval
(1552)
RUN
o5-03: Log Monitor Data 1
No.
Name
(Hex.)
o5-03
Log Monitor Data 1
(1553)
RUN
Note:
Set the number of the U monitor to record the data log.
For example, to show U1-01 [Frequency Reference], set o5-03 = 101. When it is not necessary to set data log monitors, set this
parameter to 000. You cannot set U2 monitor [Fault Trace] or U3 Monitor [Fault History].
o5-04: Log Monitor Data 2
No.
Name
(Hex.)
o5-04
Log Monitor Data 2
(1554)
RUN
Note:
Set the U monitor number you will log.
For example, to show U1-02 [Output Frequency], set o5-04 = 102. When it is not necessary to set data log monitor, set this parameter to
000.
YASKAWA SIEPC71061753A GA500 Technical Manual
Number of
Characters
12
Data log data was retrieved (YYMMDDHHMMSS)
4
Log monitor data (Hex.) of the monitor selected with o5-03 [Log Monitor Data 1]
4
Log monitor data (Hex.) of the monitor selected with o5-04 [Log Monitor Data 2]
:
:
4
Log monitor data (Hex.) of the monitor selected with o5-12 [Log Monitor Data 10]
4
-
4
Log Monitor Data 1 to 10 Code Data (Hex.)
Bits 0 through 9 show the encoding of log monitor data 1 1 through 10. A bit value of 1 shows that the data represents
a negative value. (Log monitor data 1 through 10 is absolute value data without encoding)
Example when log monitor data 2, 5, and 8 show negative values: Bits 1, 4, and 7 have values of 1, and the encoding
data = 0010010010 (Bin.) = 0092 (Hex.)
6
Row number (Hex.) in the data log file
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the data log function. This parameter is only available when using an LCD keypad.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the data log sampling cycle. This parameter is only available when using an LCD keypad.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the data log monitor. This parameter is only available when using an LCD keypad.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the data log monitor. This parameter is only available when using an LCD keypad.
12.11 o: Keypad-Related Settings
Description
Description
Description
Description
Description
Default
(Range)
0
(0 - 1)
Default
(Range)
1000 ms
(100 - 60000 ms)
Default
(Range)
101
(000, 101 - 999)
Default
(Range)
102
(000, 101 - 999)
12
747