11.10 H: Terminal Functions; H1: Digital Inputs - YASKAWA CIPR-GA50C series Technical Manual

Ac micro drives for industrial applications. 200 v class, three-phase input: 0.1 to 22 kw. 200 v class, single-phase input: 0.1 to 4.0 kw. 400 v class, three-phase input: 0.37 to 30 kw.
Table of Contents

Advertisement

11.10 H: Terminal Functions

H1: Digital Inputs

No.
Name
(Hex.)
H1-01
Terminal S1 Function
Selection
(0438)
H1-02
Terminal S2 Function
Selection
(0439)
H1-03
Terminal S3 Function
Selection
(0400)
H1-04
Terminal S4 Function
Selection
(0401)
H1-05
Terminal S5 Function
Selection
(0402)
H1-06
Terminal S6 Function
Selection
(0403)
H1-07
Terminal S7 Function
Selection
(0404)
H1-21
Terminal S1 Function
Selection 2
(0B70)
H1-22
Terminal S2 Function
Select 2
(0B71)
H1-23
Terminal S3 Function
Selection 2
(0B72)
H1-24
Terminal S4 Function
Selection 2
(0B73)
H1-25
Terminal S5 Function
Selection 2
(0B74)
H1-26
Terminal S6 Function
Selection 2
(0B75)
H1-27
Terminal S7 Function
Selection 2
(0B76)
H1-40
Mbus Reg 15C0h bit0
Input Func
(0B54)
H1-41
Mbus Reg 15C0h bit1
Input Func
(0B55)
H1-42
Mbus Reg 15C0h bit2
Input Func
(0B56)
YASKAWA SIEPC71061753A GA500 Technical Manual
Description
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the function for MFDI terminal S1.
Note:
The default setting is F when the drive is initialized for 3-Wire Initialization [A1-03
= 3330].
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the function for MFDI terminal S2.
Note:
The default setting is F when the drive is initialized for 3-Wire Initialization [A1-03
= 3330].
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the function for MFDI terminal S3.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the function for MFDI terminal S4.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the function for MFDI terminal S5.
Note:
The default setting is 0 when the drive is initialized for 3-Wire Initialization [A1-03
= 3330].
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the function for MFDI terminal S6.
Note:
When you initialize the drive for 3-Wire Initialization [A1-03 = 3330], the default
setting is 3.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the function for MFDI terminal S7.
Note:
When you initialize the drive for 3-Wire Initialization [A1-03 = 3330], the default
setting is 4.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the second function for MFDI terminal S1.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the second function for MFDI terminal S2.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the second function for MFDI terminal S3.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the second function for MFDI terminal S4.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the second function for MFDI terminal S5.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the second function for MFDI terminal S6.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the second function for MFDI terminal S7.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Selects MFDI function assigned to bit 0 of the MEMOBUS register 15C0 (Hex.).
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Selects MFDI function assigned to bit 1 of the MEMOBUS register 15C0 (Hex.).
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Selects MFDI function assigned to bit 2 of the MEMOBUS register 15C0 (Hex.).

11.10 H: Terminal Functions

Default
Ref.
(Range)
40
600
(1 - 1FF)
41
600
(1 - 1FF)
24
600
(0 - 1FF)
14
600
(0 - 1FF)
3
600
(0 - 1FF)
4
600
(0 - 1FF)
6
601
(0 - 1FF)
F
601
(1 - 19F)
F
601
(1 - 19F)
F
601
(1 - 19F)
F
601
(1 - 19F)
F
601
(1 - 19F)
F
602
(1 - 19F)
F
602
(1 - 19F)
F
602
(1 - 19F)
F
602
(1 - 19F)
F
602
(1 - 19F)
11
369

Advertisement

Table of Contents
loading

This manual is also suitable for: