H7: Virtual Mfio Selection - YASKAWA CIPR-GA50C series Technical Manual

Ac micro drives for industrial applications. 200 v class, three-phase input: 0.1 to 22 kw. 200 v class, single-phase input: 0.1 to 4.0 kw. 400 v class, three-phase input: 0.37 to 30 kw.
Table of Contents

Advertisement

H6-07: Terminal MP Frequency Scaling
No.
Name
(Hex.)
H6-07
Terminal MP Frequency
Scaling
(0432)
RUN
When H6-06 = 102 [Terminal MP Monitor Selection = Output Frequency] and H6-07 = 0, the pulse train output
terminal MP outputs the same frequency as the drive output frequency.
H6-08: Terminal RP Minimum Frequency
No.
Name
(Hex.)
H6-08
Terminal RP Minimum
Frequency
(043F)
• When you input a pulse train frequency that is less than the value of H6-08, the pulse train input is 0.0 Hz.
• Set H6-01 [Terminal RP Pulse Train Function] = 0 [Frequency Reference], 1 [PID Feedback Value], or 2 [PID
Setpoint Value] to enable this parameter.
• When H6-01 = 3 [Speed Feedback (V/F Control)], the drive applies the setting of F1-14 [Encoder Open-Circuit
Detect Time] to the minimum frequency.

H7: Virtual MFIO Selection

The virtual I/O function performs the following.
• Inputs the result of the output from the MFDO terminal to the MFDI terminal without external wiring.
• Inputs the result of the output from the MFAO terminal to the MFAI terminal without external wiring.
WARNING! Sudden Movement Hazard. Before you do a test run, make sure that the setting values for virtual input and output
function parameters are correct. Virtual input and output functions can have different default settings and operation than wired
input and output functions. Incorrect function settings can cause serious injury or death.
[Virtual Multi-Function
YASKAWA SIEPC71061753A GA500 Technical Manual
Figure 12.103 Circuit Diagram When Used as the Sinking Input
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the frequency of the pulse train output signal used when the monitor set with H6-06
[Terminal MP Monitor Selection] is 100%.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the minimum frequency of the pulse train signal that terminal RP can detect.
Figure 12.104 Virtual Analog I/O Functional Block Diagram
H7-10
Output 1]
Figure 12.105 Virtual Digital I/O Functional Block Diagram
12.8 H: Terminal Function Selection
Description
Description
H7-11
[Virtual Output
1 Delay Time]
Default
(Range)
1440 Hz
(0 - 32000 Hz)
Default
(Range)
0.5 Hz
(0.1 - 1000.0 Hz)
H7-01
[Virtual Multi-Function
Input 1]
12
661