Model Specifications (Three-Phase 200 V Class) - YASKAWA CIPR-GA50C series Technical Manual

Ac micro drives for industrial applications. 200 v class, three-phase input: 0.1 to 22 kw. 200 v class, single-phase input: 0.1 to 4.0 kw. 400 v class, three-phase input: 0.37 to 30 kw.
Table of Contents

Advertisement

10.3 Model Specifications (Three-Phase 200 V Class)

10.3

Model Specifications (Three-Phase 200 V Class)

Model
Maximum Applicable Motor Output (kW)
Maximum Applicable Motor Output (HP)
Input
Rated Input Current (A)
Rated Output Capacity
*3
(kVA)
Rated Output Current
(A)
Overload Tolerance
Output
Carrier Frequency
Maximum Output Voltage
Maximum Output Frequency
Measures for
DC reactor
Harmonics
Braking Device
Braking Transistor
EMC Filter
EMC Filter
IEC61800-3
Rated Voltage/Rated Frequency
Permitted Voltage Fluctuation
Power Supply
Permitted Frequency Fluctuation
Input Power (kVA)
*1
The maximum applicable motor output complies with 208 V motor ratings as specified in NEC Table 430.250. The rated output
current of the drive output amps must be equal to or more than the motor rated current.
*2
The maximum applicable motor output is based on 4-pole, general-purpose 220 V motor ratings. The rated output current of the drive
output amps must be equal to or more than the motor rated current.
*3
The rated output capacity is calculated with a rated output voltage of 220 V.
Model
HD
Maximum Applicable
Motor Output (kW)
ND
HD
Maximum Applicable
Motor Output (HP)
ND
HD
Rated Input
Input
Current (A)
ND
314
Table 10.2 Ratings (Three-Phase 200 V Class)
*1
HD
*2
ND
*1
HD
*2
ND
HD
ND
HD
ND
HD
ND
HD
ND
Table 10.3 Ratings (Three-Phase 200 V Class)
2010
2012
*1
1.5
2.2
*2
2.2
3
*1
2
3
*2
3
4
7.5
11
10.8
13.9
2001
2002
0.1
0.25
0.18
0.37
1/6
1/4
1/6
1/4
0.7
1.5
1.1
1.9
0.3
0.6
0.5
0.7
0.8
1.6
1.2
1.9
• HD: 150% of the rated output current for 60 seconds. The permitted frequency of overload is
once every 10 minutes.
• ND: 110% of the rated output current for 60 seconds. The permitted frequency of overload is
once every 10 minutes.
Note:
Derating may be necessary for applications that start and stop frequently.
HD: 10 kHz without derating the drive capacity.
ND: 2 kHz without derating the drive capacity.
Derate the drive capacity to use values to 15 kHz maximum.
Three-phase 200 V to 240 V
Note:
The maximum output voltage is proportional to the input voltage.
• EZOLV: 120 Hz
• AOLV/PM: 270 Hz
• V/f, OLV, OLV/PM: 590 Hz
External options
Standard internal characteristics
Factory option
Models 2xxxE: Category C3 (Conducted emission)
• Three-phase AC power supply 200 V to 240 V at 50/60 Hz 
• DC power supply 270 V to 340 V
-15% to +10%
±5%
0.3
0.7
0.5
1.2
2021
2030
2042
4.0
5.5
5.5
7.5
5
7.5
5
10
18.9
24
24
37
YASKAWA SIEPC71061753A GA500 Technical Manual
2004
0.55
0.75
1/2
3/4
2.9
3.9
1.1
1.3
3.0
3.5
1.3
1.8
2056
2070
7.5
11
15
11
15
18.5
10
15
20
10
20
25
37
52
68
52
68
80
2006
1.1
1.1
1
1.5
5.8
7.3
1.9
2.3
5.0
6
2.7
3.3
2082
18.5
22
25
30
96
114

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ga500 series

Table of Contents