n7-07: Speed Calculation Gain1
No.
Name
(Hex.)
n7-07
Speed Calculation Gain1
(3117)
Expert
n7-08: Speed Calculation Gain2
No.
Name
(Hex.)
n7-08
Speed Calculation Gain2
(3118)
Expert
Note:
When you increase the setting value, you can do a speed search of a motor rotating at a high frequency. If the setting value is too high,
the calculated speed will oscillate and a restart will fail. Decrease the setting value in these conditions.
n7-10: Pull-in Current Switching Speed
No.
Name
(Hex.)
n7-10
Pull-in Current Switching
Speed
(311A)
Expert
Note:
• When the drive accelerates, it enables these settings:
–Motor speed ≤ n7-10 + n7-11 [Drv Mode Switch Hysteresis Band]: n8-51 [Pull-in Current @ Acceleration]
–Motor speed > n7-10 + n7-11: b8-01 [Energy Saving Control Selection]
• When the drive decelerates, it enables these settings:
–Motor speed ≤ n7-10: n8-51 [Pull-in Current @ Acceleration]
–Motor speed > n7-10: b8-01 [Energy Saving Control Selection]
• If there is a large quantity of oscillation when you operate in the low speed range, increase the setting value.
• When it is most important to save energy in the low speed range, decrease the setting value.
n7-17: Resistance TemperatureCorrection
No.
Name
(Hex.)
n7-17
Resistance
TemperatureCorrection
(3122)
0 : Invalid
1 : Valid (Only 1 time)
2 : Valid (Every time)
Note:
• For settings 1 and 2, the adjustment time can cause a delay before startup.
• For settings 1 and 2, the drive can set the line-to-line resistance value of E9-10 [Motor Line-to-Line Resistance].
• When the temperature will change at startup, use setting 2.
• To decrease the startup time, set this parameter to 0, then do line-to-line resistance tuning.
• If you will start from coasting, set this parameter to 0, then do line-to-line resistance tuning.
n7-19: Flux Error Compensation Gain
No.
Name
(Hex.)
n7-19
Flux Error Compensation
Gain
(3128)
Expert
YASKAWA SIEPC71061753A GA500 Technical Manual
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the speed calculation gain during usual operation. Usually it is not necessary to change this
setting.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the speed calculation gain during a speed search.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the speed range to operate with the pull-in current command. Drive rated frequency = 100%
value. If there is a large quantity of oscillation when you operate in the low speed range, increase
the setting value.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the function to adjust for changes in the motor resistance value caused by changes in the
temperature.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the gain for magnetic flux compensation. Usually it is not necessary to change this setting.
12.10 n: Special Adjustment
Description
Description
Description
Description
Description
Default
(Range)
15.0 Hz
(1.0 - 50.0 Hz)
Default
(Range)
25.0 Hz
(1.0 - 50.0 Hz)
Default
(Range)
10.0%
(0.0 - 100.0%)
Default
(Range)
1
(0 to 2)
Default
(Range)
5000%
(0 - 50000%)
12
719