YASKAWA CIPR-GA50C series Technical Manual page 557

Ac micro drives for industrial applications. 200 v class, three-phase input: 0.1 to 22 kw. 200 v class, single-phase input: 0.1 to 4.0 kw. 400 v class, three-phase input: 0.37 to 30 kw.
Table of Contents

Advertisement

Note:
Be aware of the following points when manually setting V/f patterns.
• To set linear V/f characteristics at frequencies lower than E1-06 [Base Frequency], set E1-07 = E1-09 [Mid Point A Frequency =
Minimum Output Frequency]. In this application, the drive ignores E1-08 [Mid Point A Voltage].
• Set the five frequencies as specified by these rules: Incorrect settings will cause oPE10 [V/f Data Setting Error].
E1-09 ≤ E1-07 < E1-06 ≤ E1-11 ≤ E1-04 [Minimum Output Frequency ≤ Mid Point A Frequency < Base Frequency ≤ Mid Point B
Frequency ≤ Maximum Output Frequency]
• Setting E1-11 = 0 [Mid Point B Frequency = 0 Hz] disables E1-12 [Mid Point B Voltage]. Ensure that the four frequencies are set
according to the following rules;
E1-09 ≤ E1-07 < E1-06 ≤ E1-04
• When you use A1-03 [Initialize] to initialize the drive, it will not reset E1-03.
E1-01: Input AC Supply Voltage
No.
Name
(Hex.)
E1-01
Input AC Supply Voltage
(0300)
NOTICE: Set parameter E1-01 to align with the drive input voltage (not motor voltage). If this parameter is incorrect, the
protective functions of the drive will not operate correctly and it can cause damage to the drive.
Values Related to the Drive Input Voltage
The value set in E1-01 is the base value that the drive uses for the motor protective functions in
a 400 V class drive, the detection level changes for some motor protective functions.
Voltage
E1-01 Setting
200 V class
All settings
Setting value ≥ 400 V
400 V class
Setting value < 400 V
*1
This is the protection function enabled in drives with built-in braking transistors. These values show the level that will trigger the
built-in braking transistor. Refer to "YASKAWA AC Drive 72060001 Series Option Braking Unit and Braking Resistor Unit
Installation Manual (TOBPC72060001)" for more information.
E1-03: V/f Pattern Selection
No.
Name
(Hex.)
E1-03
V/f Pattern Selection
(0302)
Note:
• When A1-02 = 2 [Control Method Selection = OLV], settings 0 to E are not available.
• Set the correct V/f pattern for the application and operation area. An incorrect V/f pattern can decrease motor torque and increase
current from overexcitation.
• Parameter A1-03 [Initialize Parameters] will not reset the value of E1-03.
0 : Const Trq, 50Hz base, 50Hz max
YASKAWA SIEPC71061753A GA500 Technical Manual
Figure 12.60 V/f Pattern
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the drive input voltage.
Table 12.46 Values Related to the Drive Input Voltage
BTR Operation
Level
ov Detection Level
(rr Detection Level)
*1
410 V
394 V
820 V
788 V
820 V
788 V
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the V/f pattern for the drive and motor. You can use one of the preset patterns or you can
make a custom pattern.
Description
Approximate Values
L2-05
[Undervoltage
Detection Lvl (Uv1)]
Voltage Setpoint]
190 V
380 V
350 V
Description
12.6 E: Motor Parameters
Default
(Range)
200 V Class: 230 V, 400 V:
400 V
(200 V Class: 155 to 255 V,
400 V Class: 310 to 510 V)
Table
12.46. With
L2-11
L3-17
[KEB DC Bus
[DC Bus Regulation
Level]
260 V
375 V
500 V
750 V
460 V
750 V
Default
(Range)
F
(Determined by A1-02)
12
557

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ga500 series

Table of Contents