YASKAWA CIPR-GA50C series Technical Manual page 585

Ac micro drives for industrial applications. 200 v class, three-phase input: 0.1 to 22 kw. 200 v class, single-phase input: 0.1 to 4.0 kw. 400 v class, three-phase input: 0.37 to 30 kw.
Table of Contents

Advertisement

The keypad shows EF0 and the drive continues operation.
Note:
Separately prepare safety protection equipment and systems, for example fast stop switches.
The output terminal set to Alarm [H2-01 to H2-03 = 10] activates.
F6-04: bUS Error Detection Time
No.
Name
(Hex.)
F6-04
bUS Error Detection Time
(03A5)
Note:
When you install an option card in the drive, the parameter value changes to 0.0 s.
F6-06: Torque Reference/Limit by Comm
No.
Name
(Hex.)
F6-06
Torque Reference/Limit by
Comm
(03A7)
0 : Disabled
1 : Enabled
F6-07: Multi-Step Ref @ NetRef/ComRef
No.
Name
(Hex.)
F6-07
Multi-Step Ref @ NetRef/
ComRef
(03A8)
0 : Disable Multi-Step References
When NetRef or ComRef are the frequency reference source, the multi-step speed reference (2-step speed to 16-
step speed references) and the Jog Frequency Reference (JOG command) are disabled.
1 : Enable Multi-Step References
When NetRef or ComRef are the frequency reference source, the multi-step speed reference (2-step speed through
16-step speed references) and the Jog Frequency Reference (JOG command) are enabled, and you can change the
frequency reference.
F6-08: Comm Parameter Reset @Initialize
No.
Name
(Hex.)
F6-08
Comm Parameter Reset
@Initialize
(036A)
0 : No Reset - Parameters Retained
1 : Reset Back to Factory Default
Note:
When you use A1-03 to initialize the drive, this setting will not change.
F6-10: CC-Link Node Address
No.
Name
(Hex.)
F6-10
CC-Link Node Address
(03B6)
Note:
Be sure to set a node address that is different than all other node addresses. Do not set this parameter to 0. Incorrect parameter settings
will cause AEr [Station Address Setting Error] errors and the L.ERR LED on the option will come on.
YASKAWA SIEPC71061753A GA500 Technical Manual
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the delay time for the drive to detect bUS [Option Communication Error].
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the function that enables and disables the torque reference and torque limit received from the
communication option.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the function that enables and disables the multi-step speed reference when the freqency
reference source is NetRef or ComRef (communication option card or MEMOBUS/Modbus
communications).
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the function to initialize F6-xx and F7-xx parameters when the drive is initialized with A1-03
[Initialize Parameters].
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the node address for CC-Link communication. Restart the drive after you change the
parameter setting.
Description
Description
Description
Description
Description
12.7 F: Options
Default
(Range)
2.0 s
(0.0 - 12.0 s)
Default
(Range)
0
(0, 1)
Default
(Range)
1
(0, 1)
Default
(Range)
0
(0, 1)
Default
(Range)
0
(0 - 64)
12
585

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ga500 series

Table of Contents