12.8 H: Terminal Function Selection
17: Fast Stop (N.C.)
Setting Value
Function
17
Fast Stop (N.C.)
If you cancel the fast stop input, the drive will not restart the motor until you meet these conditions:
• Fully stop the motor
• Cancel the Run command
• Cancel the fast stop command
Note:
• To use the N.O. switch to input the fast stop command, set 15 (Fast Stop (N.O.)).
• For details, refer to C1-09 [Fast Stop Time].
• Set C1-09 [Fast Stop Time] to a correct deceleration time. If the deceleration time is too short, it can cause an overvoltage fault and
failure to stop the motor from coasting.
Figure 12.69
shows an example of how fast stop operates.
18: Timer Function
Setting Value
Function
18
Timer Function
Note:
Refer to "b4: Timer Function" for more information.
19: PID Disable
Setting Value
Function
19
PID Disable
ON : PID control disabled
OFF : PID control enabled
1A: Accel/Decel Time Selection 2
Setting Value
Function
1A
Accel/Decel Time Selection
2
Note:
Refer to "C1: Accel & Decel Time" for more information.
1B: Programming Lockout
Setting Value
Function
1B
Programming Lockout
610
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the command to ramp to stop in the deceleration time set in C1-09 [Fast Stop Time] when the input terminal is activated
while the drive is operating.
Figure 12.69 Fast Stop Time Chart
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the command to start the timer function. Use this setting with Timer Output [H2-xx = 12].
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the command to disable PID control when b5-01 = 1 to 8 [PID Mode Setting = Enabled].
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Set this function and H1-xx = 7[Accel/Decel Time Selection 1] together. Sets the drive to use Acceleration/Deceleration Time 3
[C1-05, C1-06] or Acceleration/Deceleration Time 4 [C1-07, C1-08].
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the command to prevent parameter changes when the terminal is OFF.
Description
Description
Description
Description
Description
YASKAWA SIEPC71061753A GA500 Technical Manual