H3-12: Terminal A2 Bias Setting
No.
Name
(Hex.)
H3-12
Terminal A2 Bias Setting
(041A)
RUN
When 0 V (4 mA or 0 mA) is input, this parameter sets the bias for the function set for terminal A2 as a
percentage.
Use this parameter and H3-11 [Terminal A2 Gain Setting] to adjust the characteristics of the analog input signal to
terminal A2.
H3-13: Analog Input FilterTime Constant
No.
Name
(Hex.)
H3-13
Analog Input FilterTime
Constant
(041B)
Apply the primary delay filter to the analog input to enable an analog input signal without the use of high-
frequency noise components. An analog input filter prevents irregular drive control. Drive operation becomes
more stable as the programmed time becomes longer, but it also becomes less responsive to quickly changing
analog signals.
H3-14: Analog Input Terminal Enable Sel
No.
Name
(Hex.)
H3-14
Analog Input Terminal
Enable Sel
(041C)
Input signals do not have an effect on terminals not set as targets.
1 : Terminal A1 only
2 : Terminal A2 only
7 : Terminals A1 and A2
Note:
• The ON/OFF operation of terminal Sx set in Analog Terminal Input Selection [H1-xx = C] has an effect on only the analog input
terminal selected with H3-14.
• When H1-xx ≠ C, the functions set to terminals A1 and A2 are always enabled.
H3-16: Terminal A1 Offset
No.
Name
(Hex.)
H3-16
Terminal A1 Offset
(02F0)
Adds the offset value for the analog input value. For voltage input, this parameter will set the offset when a signal
of 0 V is input.
H3-17: Terminal A2 Offset
No.
Name
(Hex.)
H3-17
Terminal A2 Offset
(02F1)
Adds the offset value for the analog input value. For voltage input, this parameter will set the offset when a signal
of 0 V is input. For current input, this parameter will set the offset when a signal of 4 mA [H3-09 = 2] or 0 mA
[H3-09 = 3] is input.
YASKAWA SIEPC71061753A GA500 Technical Manual
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the bias of the analog signal input to MFAI terminal A2.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the time constant for primary delay filters on MFAI terminals.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the enabled terminal or terminals when H1-xx = C [MFDI Function Select = Analog
Terminal Enable Selection] is ON.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the offset level for analog signals input to terminal A1. Usually it is not necessary to change
this setting.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the offset level for analog signals input to terminal A2. Usually it is not necessary to change
this setting.
12.8 H: Terminal Function Selection
Description
Description
Description
Description
Description
Default
(Range)
0.0%
(-999.9 - +999.9%)
Default
(Range)
0.03 s
(0.00 - 2.00 s)
Default
(Range)
7
(1, 2, 7)
Default
(Range)
0
(-500 - +500)
Default
(Range)
0
(-500 - +500)
12