YASKAWA CIPR-GA50C series Technical Manual page 383

Ac micro drives for industrial applications. 200 v class, three-phase input: 0.1 to 22 kw. 200 v class, single-phase input: 0.1 to 4.0 kw. 400 v class, three-phase input: 0.37 to 30 kw.
Table of Contents

Advertisement

No.
Name
(Hex.)
H5-03
Communication Parity
Selection
(0427)
H5-04
Communication Error
Stop Method
(0428)
H5-05
Comm Fault Detection
Selection
(0429)
H5-06
Drive Transmit Wait
Time
(042A)
H5-09
CE Detection Time
(0435)
H5-10
Modbus Register 0025H
Unit Sel
(0436)
H5-11
Comm ENTER
Command Mode
(043C)
RUN
H5-12
Run Command Method
Selection
(043D)
H5-17
ENTER command
response @CPU BUSY
(11A1)
Expert
H5-18
Motor Speed Filter over
Comms
(11A2)
H5-20
Communication
Parameters Reload
(0B57)
H5-22
Speed Search from
MODBUS
(11CF)
H5-25
Function 5A Register 1
Selection
(1589)
RUN
H5-26
Function 5A Register 2
Selection
(158A)
RUN
YASKAWA SIEPC71061753A GA500 Technical Manual
Description
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the communications parity used for MEMOBUS/Modbus communications.
Note:
Restart the drive after changing the parameter setting.
0 : No parity
1 : Even parity
2 : Odd parity
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the motor Stopping Method when the drive detects CE [MEMOBUS/Modbus
Communication Err] issues.
0 : Ramp to Stop
1 : Coast to Stop
2 : Fast Stop (Use C1-09)
3 : Alarm Only
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the function that detects CE [Modbus Communication Error] issues during
MEMOBUS/Modbus communications.
0 : Disabled
1 : Enabled
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the time to wait to send a response message after the drive receives a command
message from the master.
Note:
Restart the drive after changing the parameter setting.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the detection time for CE [Modbus Communication Error] issues when
communication stops.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the unit of measure used for the MEMOBUS/Modbus communications monitor
register 0025H (output voltage reference monitor).
0 : 0.1 V units
1 : 1 V units
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the function to make the Enter command necessary to change parameters through
MEMOBUS/Modbus communications.
0 : ENTER Command Required
1 : ENTER Command Not Required
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the input method for the Run command when b1-02 = 2 [Run Command Selection
1 = Memobus/Modbus Communications] or b1-16 = 2 [Run Command Selection 2 =
Memobus/Modbus Communications].
0 : FWD/Stop, REV/Stop
1 : Run/Stop, FWD/REV
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets operation when the EEPROM write command is sent without EEPROM write
available. Usually it is not necessary to change this setting.
0 : Ignore Command(No ROM/RAM Write)
1 : Write to RAM Only
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the filter time constant used when monitoring motor speed during MEMOBUS/
Modbus communications or with a communication option.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the function to immediately enable updated MEMOBUS/Modbus communications
parameters.
0 : Reload at Next Power Cycle
1 : Reload Now
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Enables the MEMOBUS/Modbus communication register Speed Search function (bit0
of 15DFH).
0 : Disabled
1 : Enabled
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Returns the contents of the specified MEMOBUS/Modbus communications register
when responding to the master device.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Returns the contents of the specified MEMOBUS/Modbus communications register
when responding to the master device.
11.10 H: Terminal Functions
Default
Ref.
(Range)
0
655
(0 - 2)
3
655
(0 - 3)
1
655
(0, 1)
5 ms
655
(0 - 65 ms)
2.0 s
656
(0.0 - 25.0 s)
0
656
(0, 1)
0
656
(0, 1)
0
656
(0, 1)
0
657
(0, 1)
0 ms
657
(0 - 100 ms)
0
657
(0, 1)
0
657
(0, 1)
0044H (U1-05)
658
(0000H - FFFFH)
0045H (U1-06)
658
(0000H - FFFFH)
11
383