YASKAWA CIPR-GA50C series Technical Manual page 221

Ac micro drives for industrial applications. 200 v class, three-phase input: 0.1 to 22 kw. 200 v class, single-phase input: 0.1 to 4.0 kw. 400 v class, three-phase input: 0.37 to 30 kw.
Table of Contents

Advertisement

Register No.
(Hex.)
Drive Status 1
bit 0
bit 1
bit 2
bit 3
bit 4
0020
bit 5
bit 6
bit 7
bit 8 - D
bit E
bit F
Fault Description 1
bit 0
bit 1
bit 2
bit 3
bit 4
bit 5
bit 6
bit 7
0021
bit 8
bit 9
bit A
bit B
bit C
bit D
bit E
bit F
YASKAWA SIEPC71061753A GA500 Technical Manual
Table 6.12 Monitor Data for MEMOBUS/Modbus Communication
During Run
1: During run, 0: During stop
During reverse
1: During reverse, 0: Forward run
Drive ready
1: Ready, 0: Not ready
Fault
1: Fault
Data Setting Error
1: oPExx error
MFDO (terminal MA/MB-MC)
1: ON, 0: OFF
Multi-function photocoupler output 1 (terminal P1-C1)
1: ON, 0: OFF
Multi-function photocoupler output 2 (terminal P2-C2)
1: ON, 0: OFF
Reserved
ComRef status
1: Enabled
ComCtrl status
1: Enabled
oC [Overcurrent], GF [Ground Fault]
ov [Overvoltage]
oL2 [Drive Overload]
oH1 [Heatsink Overheat], oH2 [External Overheat (H1-XX=B)]
rH [Braking Resistor Overheat], rr [Dynamic Braking Transistor Fault]
Reserved
FbL [PID Feedback Loss], FbH [Excessive PID Feedback]
EF0 [Option Card External Fault], EF1 to EF7 [External Fault]
CPFxx [Hardware Fault]
Note:
Includes oFx.
oL1 [Motor Overload], oL3, oL4 [Overtorque Detection 1/2], UL3, UL4 [Undertorque Detection 1/2]
PGo [Encoder (PG) Feedback Loss], oS [Overspeed], dEv [Speed Deviation]
During Uv [Undervoltage] detection
Uv1 [DC Bus Undervoltage], Uv2 [Control Power Undervoltage], Uv3 [Soft Charge Answerback Fault]
LF [Output Phase Loss], PF [Input Phase Loss]
CE [Modbus Communication Error], bUS [Option Communication Error]
Reserved
6.3 MEMOBUS/Modbus Communications
Description
6
221