YASKAWA CIPR-GA50C series Technical Manual page 725

Ac micro drives for industrial applications. 200 v class, three-phase input: 0.1 to 22 kw. 200 v class, single-phase input: 0.1 to 4.0 kw. 400 v class, three-phase input: 0.37 to 30 kw.
Table of Contents

Advertisement

n8-63: Output Voltage Limit P Gain
No.
Name
(Hex.)
n8-63
Output Voltage Limit P
Gain
(057E)
Expert
n8-65: Speed Fdbk Gain @ oV Suppression
No.
Name
(Hex.)
n8-65
Speed Fdbk Gain @ oV
Suppression
(065C)
Expert
Adjust this parameter in these conditions:
• If there is resonance or hunting when you use the overvoltage suppression function, increase the setting value.
• If motor response is low when you use the overvoltage suppression function, decrease the setting value in 0.05-
unit increments.
n8-69: Speed Observer Control P Gain
No.
Name
(Hex.)
n8-69
Speed Observer Control P
Gain
(065D)
Expert
n8-72: Speed Estimation Method Select
No.
Name
(Hex.)
n8-72
Speed Estimation Method
Select
(0655)
Expert
0 : Method 1
1 : Method 2
n8-74: Light Load Iq Level
No.
Name
(Hex.)
n8-74
Light Load Iq Level
(05C3)
Expert
Note:
• If n8-74 > n8-75 [Medium Load Iq Level (low)], the drive will detect oPE08 [Parameter Selection Error].
• The change is linear between n8-74 and n8-75 and the level of the pull-in current from n8-48 to n8-78 [Medium Load Id Current].
n8-75: Medium Load Iq Level (low)
No.
Name
(Hex.)
n8-75
Medium Load Iq Level
(low)
(05C4)
Expert
Note:
• If n8-74 [Light Load Iq Level] > n8-75, the drive will detect oPE08 [Parameter Selection Error].
• The change is linear between n8-74 and n8-75 and the level of the pull-in current from n8-48 to n8-78 [Medium Load Id Current].
YASKAWA SIEPC71061753A GA500 Technical Manual
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the proportional gain for output voltage control. Usually it is not necessary to change this
setting.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the gain of internal speed feedback detection suppression while the overvoltage suppression
function is operating as a magnification value. Usually it is not necessary to change this
parameter.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Usually it is not necessary to change this setting. Sets the Proportional gain that the drive uses for
speed estimation.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Selects the speed estimation method. Usually it is not necessary to change this setting.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Set n8-48 [Pull-in/Light Load Id Current] to the percentage of load current (q-axis current) that
you will apply, where E5-03 [Motor Rated Current (FLA)] = a setting value of 100%.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Set n8-78 [Medium Load Id Current] to the percentage of load current (q-axis current) that you
will apply, where E5-03 [Motor Rated Current (FLA)] = a setting value of 100%.
12.10 n: Special Adjustment
Description
Description
Description
Description
Description
Description
Default
(Range)
1.00
(0.00 - 100.00)
Default
(Range)
1.50
(0.00 - 10.00)
Default
(Range)
1.00
(0.00 - 20.00)
Default
(Range)
1
(0, 1)
Default
(Range)
30%
(0 - 255%)
Default
(Range)
50%
(0 - 255%)
12
725