d2: Reference Limits

d2 parameters set the upper and lower frequency limits to control the motor speed. Apply these parameters to for
example, run the motor at low-speed due to mechanical strength concerns, or if the motor should not be run at low
speed because of lubrication issues with the gears and bearings.
The upper frequency limit is set in d2-01 [Frequency Reference Upper Limit] and the lower limit is set in d2-02
[Frequency Reference Lower Limit].
d2-01: Frequency Reference Upper Limit
No.
Name
(Hex.)
d2-01
Frequency Reference Upper
Limit
(0289)
When the frequency reference is more than the value set in d2-01 the drive will continue to operate at the value set
in d2-01.
d2-02: Frequency Reference Lower Limit
No.
Name
(Hex.)
d2-02
Frequency Reference
Lower Limit
(028A)
When the frequency reference is less than the value set in d2-02, the drive will continue to operate at the value set
in d2-02. The motor will accelerate to the d2-02 value after the drive receives a Run command and a lower
frequency reference than d2-02 has been entered.
d2-03: Analog Frequency Ref Lower Limit
No.
Name
(Hex.)
d2-03
Analog Frequency Ref
Lower Limit
(0293)
This parameter does not change the lower limit of Jog reference, frequency reference for multi-step speed
operation, or the auxiliary frequency reference.
The drive operates at the value set in d2-03 when the frequency reference decreases to less than the value set in
d2-03.
Note:
When lower limits are set to parameters d2-02 [Frequency Reference Lower Limit] and d2-03, the drive uses the larger value as the
lower limit.

d3: Jump Frequency

The Jump frequency is a function that sets the dead band to a specified frequency band. If a machine that operated
at constant speed is operated with variable speed, it can make resonance. To operate the machine without
resonance from the natural frequency of the machinery mechanical system, use a frequency band jump.
You can program the drive to have three different Jump frequencies. Set d3-01 to d3-03 [Jump Frequencies] to
the median value for the jumped frequency and set d3-04 [Jump Frequency Width] to the Jump frequency width.
When you input a frequency reference that is the same as or near the Jump frequency width, the frequency
reference changes automatically.
546
Figure 12.50 Upper and Lower Frequency Limits
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets maximum limit for all frequency references. The maximum output frequency is 100%.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets minimum limit for all frequency references. The maximum output frequency is 100%.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the lower limit for the master frequency reference (the first frequency of the multi-step speed
reference) as a percentage. The maximum output frequency is 100%.
Description
Description
Description
YASKAWA SIEPC71061753A GA500 Technical Manual
Default
(Range)
100.0%
(0.0 - 110.0%)
Default
(Range)
0.0%
(0.0 - 110.0%)
Default
(Range)
0.0%
(0.0 - 110.0%)