11.10 H: Terminal Functions
H1-xx: MFDI Setting Values
Setting Value
Function
0
3-Wire Sequence
1
LOCAL/REMOTE
Selection
2
External Reference 1/2
Selection
3
Multi-Step Speed
Reference 1
4
Multi-Step Speed
Reference 2
5
Multi-Step Speed
Reference 3
6
Jog Reference Selection
7
Accel/Decel Time
Selection 1
8
Baseblock Command
(N.O.)
9
Baseblock Command
(N.C.)
A
Accel/Decel Ramp Hold
B
Overheat Alarm (oH2)
C
Analog Terminal Enable
Selection
E
ASR Integral Reset
F
Not Used
10
Up Command
11
Down Command
12
Forward Jog
13
Reverse Jog
370
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the direction of motor rotation for 3-wire sequence.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets drive control for the keypad (LOCAL) or an external source (REMOTE).
ON : LOCAL
OFF : REMOTE
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the drive to use Run command source 1/2 or Reference command source 1/2 when in REMOTE Mode.
ON : b1-15 = [Frequency Reference Selection 2], b1-16 [Run Command Selection 2]
OFF : b1-01 = [Frequency Reference Selection 1], b1-02 [Run Command Selection 1]
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Uses speed references d1-01 to d1-16 to set a multi-step speed reference.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Uses speed references d1-01 to d1-16 to set a multi-step speed reference.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Uses speed references d1-01 to d1-16 to set a multi-step speed reference.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the drive to use the JOG Frequency Reference (JOG command) set in d1-17. The JOG Frequency Reference
(JOG command) overrides Frequency References 1 to 16 (d1-01 to d1-16).
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the drive to use Acceleration/Deceleration Time 1 [C1-01, C1-02] or Acceleration/Deceleration Time 2 [C1-
03, C1-04].
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the command that stops drive output and coasts the motor to stop when the input is ON.
ON : Baseblock (drive output stop)
OFF : Normal operation
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the command that stops drive output and coasts the motor to stop when the input terminal is OFF.
ON : Normal operation
OFF : Baseblock (drive output stop)
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Momentarily pauses motor acceleration and deceleration when the terminal is turned ON, retains the output
frequency that was stored in the drive at the time of the pause, and restarts motor operation.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the drive to display an oH2 [Drive Overheat Warning] alarm when the input terminal is ON. The alarm does
not have an effect on drive operation.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the command that enables or disables the terminals selected in H3-14 [Analog Input Terminal Enable Sel].
ON : Input to the terminal selected with H3-14 is enabled
OFF : Input to the terminal selected with H3-14 is disabled
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the command to reset the integral value and use PI control or P control for the speed control loop.
ON : P control
OFF : PI control
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Use this setting for unused terminals or to use terminals in through mode.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the command to use a push button switch to increase the drive frequency reference. You must also set Setting
11 [Down Command].
ON : Increases the frequency reference.
OFF : Holds the current frequency reference.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the command to use a push button switch to decrease the drive frequency reference. You must also set Setting
10 [Up Command].
ON : Decreases the frequency reference.
OFF : Holds the current frequency reference.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the command to operate the motor in the forward direction at the Jog Frequency set in d1-17 [Jog Reference].
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the command to operate the motor in reverse at the Jog Frequency set in d1-17 [Jog Reference].
Description
YASKAWA SIEPC71061753A GA500 Technical Manual
Ref.
602
603
604
604
604
604
604
604
604
605
605
605
605
606
606
606
607
608
608

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ga500 series

Table of Contents