YASKAWA CIPR-GA50C series Technical Manual page 575

Ac micro drives for industrial applications. 200 v class, three-phase input: 0.1 to 22 kw. 200 v class, single-phase input: 0.1 to 4.0 kw. 400 v class, three-phase input: 0.37 to 30 kw.
Table of Contents

Advertisement

Auto-Tuning automatically sets this parameter to the value of [Number of Motor Poles].
E9-09: Motor Rated Slip
No.
Name
(Hex.)
E9-09
Motor Rated Slip
(11EC)
The setting value of this parameter is the slip compensation reference value.
The drive uses the setting values of E9-03, E9-04, and E9-08 to calculate this parameter. When Motor Rated Slip
= 0, Auto-Tuning automatically sets this parameter to the value of [Motor Rated Slip].
Note:
Set E9-01 = 0 [Motor Type Selection = Induction (IM)] before you set this parameter.
E9-10: Motor Line-to-Line Resistance
No.
Name
(Hex.)
E9-10
Motor Line-to-Line
Resistance
(11ED)
Note:
This value is the motor line-to-line resistance. Do not set this parameter with the single-phase resistance.
Stationary Auto-Tuning automatically sets this parameter. If you cannot do Stationary Auto-Tuning, use the test
report from the motor manufacturer. You can calculate the motor line-to-line resistance with one of these
formulas:
• E-type insulation: the resistance value (Ω) shown on the test report at 75 °C × 0.92
• B-type insulation: the resistance value (Ω) shown on the test report at 75 °C × 0.92
• F-type insulation: the resistance value (Ω) shown on the test report at 115 °C × 0.87
YASKAWA SIEPC71061753A GA500 Technical Manual
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the motor rated slip.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the line-to-line resistance for the motor stator windings.
Description
Description
12.6 E: Motor Parameters
Default
(Range)
0.000 Hz
(0.000 - 20.000 Hz)
Default
(Range)
Determined by o2-04
(0.000 - 65.000 Ω)
575
12