3.4 Main Circuit Terminal Block Wiring Procedure
• Do not let strain on the wiring cause damage. Use a strain relief near the wiring to release the tension. Refer to
Figure 3.31
for an example.
A - Cable clamp
Screw
Screw Shape
Size
M3
M4
*1
M5
M6
(WAF: 5 mm)
*1
When you wire drive models 2042, 2056, 4031, 4038, 4044, and 4060, select the correct tools for the wire gauge.
*2
Use 6.35 mm (0.25 in) bit socket holder.
*3
Use a torque wrench that can apply this torque measurement range.
Main Circuit Terminal Block Wiring Procedure
When terminals R/L1, S/L2, T/L3, -, +1, and +2 have IP20 protection covers, remove them.
1.
Put a wire with prepared ends into the main circuit terminal block.
Look through the opening in the drive case to make sure that you correctly installed the wires into the
terminal block.
Note:
There is a jumper between terminals +1 and +2. Remove the jumper, then wire to terminals +1 and +2.
80
Figure 3.31 Strain Relief Example
Table 3.5 Recommended Wiring Tools
Wire Gauge
Adapter
-
Bit
SF-BIT-SL 0,5X3,0-70
-
Bit
SF-BIT-SL 1,0X4,0-70
≤ 25 mm
2
(AWG 10)
Bit
SF-BIT-SL 1,2X6,5-70
2
≥ 30 mm
(AWG 8)
-
Bit
SF-BIT-HEX 5-50
Figure 3.32 Install the Electrical Wire
Bit
Model
Manufacturer
PHOENIX CONTACT
PHOENIX CONTACT
PHOENIX CONTACT
PHOENIX CONTACT
YASKAWA SIEPC71061753A GA500 Technical Manual
Torque Driver Model
Torque Wrench
(Tightening Torque)
(Tightening Torque)
TSD-M 1,2NM
(0.3 - 1.2 N∙m
(2.7 - 10.6 in∙lb))
TSD-M 3NM
(1.2 - 3.0 N∙m
(10.6 - 26.6 in∙lb))
TSD-M 3NM
(1.2 - 3.0 N∙m
(10.6 - 26.6 in∙lb))
4.1 - 4.5 N∙m
-
(36.3 - 39.8 in∙lb)
5 - 9 N∙m
-
(44.3 - 79.7 in∙lb)
-
-
-
*2 *3
*2 *3